Air Handler Selection Example
Figure 1 shows a typical peformance table for a heat 
pump air handler.  Suppose the evaporator temperature 
required is 50ºF, the capacity required is 35,000 Btuh 
and the airfl ow required is 1,200 CFM. Each evaporator 
temperature listed in the table shows three wet bulb 
temperatures. As recommended in the table notes 
above, select the 67ºF WB column.  At 1,200 CFM, the 
model 003 capacity is 36 MBtuh, which is higher than 
the minimum capacity required of 35,000 Btuh. In this 
example, model 003 would be the appropriate match. 
Figure 1: Selecting Air Handler
Utilizing the Existing Air Handler or Coil (R22 units only)
It is recommended that a new coil or air handler be 
installed with any geothermal split system compressor 
section due to the low initial cost of the additional 
equipment versus the reliability and benefi t of new 
technology, increased reliability and warranty. However, if 
the existing air handler must be used (R22 systems only), 
the following conditions apply:
•  If the existing coil currently uses an orifi ce, the orifi ce 
must be removed and replaced with a TXV. If the coil 
utilizes capillary tubes, it will not operate properly with 
the geothermal split system and should be replaced.
•  If life expectancy of indoor coil (and associated 
components - fan, cabinet, etc.) is less than 7-10 years, 
indoor section should be replaced.
Equipment Selection 
Selecting Air Handler