Simon Security System
40
Note  
Changing this setting does 
not affect speaker volume.
This option can be set from 01 - 10. Entries must be 2 digits.
¾
To set VOX Receiver Gain, press:
Add—Option #—78—1 - 10—DONE.
¾
To reset VOX Receiver Gain (return to default), press:
Delete—Option #—78—DONE.
Option 79: Panel Cover Tamper (Default = off)
Determines whether the panel activates a tamper alarm anytime the cover is opened 
(on), or only when the system is armed (off).
To enter program mode when this option is on, you must first enter the Master Access 
code, then open the cover and enter program mode within 10 seconds.
¾
To turn on Panel Cover Tamper, press:
Add—Option #—79—DONE.
¾
To turn off Panel Cover Tamper (return to default), press:
Delete—Option #—79—DONE.
Option 80: Alarm Report Verification (Default = off)
Determines whether the panel verifies successful alarm reports to the central station/
pager with the voice message “Phone communication okay” (on), or not (off).
¾
To turn on Alarm Report Verification, press:
Add—Option #—80—DONE.
¾
To turn off Alarm Report Verification (return to default), press:
Delete—Option #—80—DONE.
Option 81: Heating Set Point (Default = off)
If the room temperature falls below the Heating Set Point, the RF Electronic Thermo-
stat will turn the furnace on until the room temperature returns to the Heating Set 
Point.
¾
To adjust Heating Set Point, press:
Add—Option #—81—51 - 91—DONE.
¾
To turn off Heating Set Point (return to default), press:
Delete—Option #—81—DONE.
Option 82: Cooling Set Point (Default = off)
If the room temperature rises above the Cooling Set Point, the RF Electronic Thermo-
stat will turn the air conditioner on until the room temperature returns to the Cooling 
Set Point.
¾
To adjust Cooling Set Point, press:
Add—Option #—82—51 - 91—DONE.
¾
To turn off Cooling Set Point (return to default), press:
Delete—Option #—82—DONE.