Controlled Electronic Management Systems Ltd INFOPROX 사용자 설명서
Configuring the Door Control Unit
InfoProx Entry
Door Close After Time
Door Close After Time allows you to configure the length of time the door can
remain open before an alarm is activated.
remain open before an alarm is activated.
Modifying the door close after time option
After the door strike time is set, the following prompt appears:
Set Drclose=15s
New Drclose= s
New Drclose= s
To manually access Door Close after Time, press # when in Door Strike
Time mode.
Time mode.
To change from the default setting of 15 seconds:
1.
Enter seconds using two digits. This option can be bypassed by
pressing the # key, accepting the default. The
pressing the # key, accepting the default. The
Ù key can be used to
correct any errors made while entering the Door close after Time.
Door Close After Time is also known as Door Held
Time or Shunt Time.
Time or Shunt Time.
Once the time is set, the next screen in the Configuration menu
sequence, GIN Configuration, automatically displays.
sequence, GIN Configuration, automatically displays.