Trinamic TMC603-EVAL evaluation Board TMC603-EVAL 데이터 시트

제품 코드
TMC603-EVAL
다운로드
페이지 25
TMC603-EVAL MANUAL (V. 1.01 / April 14th, 2009) 
19 
 
 
Copyright © 2009 TRINAMIC Motion Control GmbH & Co. KG 
6.5  An example 
In  this  example  it  is  assumed  that  the  QMot  Motor  QBL4208-41-04-006  is  connected  to  the  motor 
output connector. The evaluation board is connected to an RS232 interface of the PC by using a null 
modem cable. The board is supplied with 24V (DC). 
 
At first, we would like to use the sensorless block commutation with hallFX
™ to run the BLDC motor. 
Please  check  if  the  jumpers  X212,  X213  and  X214  are  plugged.  Then  start  the  PC  software  and 
establish a connection between the evaluation board and the PC. 
 
Thereafter  set  the  operating  mode  to  “Block,  HallFX,  Closed  Loop”  to  ramp  up  with  block 
commutation  and  closed  loop  current  control.  Then  enter  the  parameters  as  shown  in  Figure  14. 
Please keep in mind to press the “Set” buttons. Thereafter, press the “Start” button and the motor will 
ramp  up  via  closed  loop  current  control  and  will  run  by  using  the  sensorless  BLDC  back  EMF 
commutation hallFX™. 
 
 
Figure 14: Parameter settings for closed loop current control (Example: QMot QBL4208-41-04-006) 
 
After  startup,  the  motor  accelerate  up  to  the  defined  speed  reference  value  (Speed  Ref.).  In  this 
example the speed reference value is set to 3000rpm. The PWM duty cycle is about 62 % dependent 
on the mechanical load.  
 
Now, we would like to disable the speed control. Please deactivate the option “Enable speed control” 
and  set  the  duty  cycle  referenc
e  value  (Duty  Cycle  Ref.)  to  62  %.  Then  press  the  “Set”  button.  The 
motor  will  run  without  speed  control.  The  PWM  duty  cycle  is  fixed.  You  can  change  the  PWM  duty 
cycle by setting a new duty cycle reference value (Duty Cycle Ref.).  
 
If you would like to start the BLDC motor with sinusoidal commutation, an initialization for sine startup 
is  required.  Select  the  operating  mode  “Block,  HallFX,  Closed  Loop”  and  enter  the  parameters  as 
shown  in  Figure  14
.  Please  check  the  option  “Enable  speed  control”.  The  speed  control  should  be 
enabled. If the speed control is disabled, the motor will start without ramp up. Please keep in mind to 
press  the  “Set”  buttons.  Thereafter,  press  the  “Start”  button  and  the  motor  will  ramp  up  with  block 
commutation.  If  the  motor  is  running  the  initialization  is  successful.  Then  stop  the  motor  by  pressing 
the “Stop” button und select the operating mode “Sine, HallFX, Closed Loop”. Thereafter, press the 
“Start”  button  and  the  motor  will  ramp  up  with  sinusoidal  commutation  and  will  run  by  using  the 
sensorless 
BLDC back EMF commutation hallFX™.