If the Retentivity option is not available, then delete the block and insert a new special
function hours counter at the same position.
0BA0-0BA5:
The maintenance interval (MI) and the start time for the operating time (OT)
The maintenance interval (MI) and the start time for the operating time (OT)
were in units of hours. These values could not be provided by another function
prior to the 0BA6 device series.
Value reset
If you download a circuit program that contains an hours counter function from LOGO!Soft
Comfort to a LOGO! 0BA7 or LOGO! 0BA8 Base Module, LOGO!Soft Comfort prompts you
whether to continue or not. If you continue with the download, the hours counter value is
reset.
Note
If you copy a circuit program that contains an hours counter function from an SD card to a
If you copy a circuit program that contains an hours counter function from an SD card to a
LOGO! Base Module, the hours counter value is reset with no notification.
Special functions (Page 212)
5.3.2.3
Threshold trigger
Short description
The output is switched on and off depending on two configurable frequencies.
Connection
Description
Input Fre
The function counts 0 to 1 transitions at input Fre. Transitions from 1 to 0 are not
counted.
•
•
Use the inputs I3, I4, I5, and I6 for high-frequency counts (LOGO!
12/24RC/RCo, LOGO! 12/24RCE, LOGO! 24/24o and LOGO! 24C/24Co):
max 5kHz, if the fast input is directly connected to the threshold trigger
function block
•
Use any other input or circuit element for low frequencies (typical 4 Hz).