HP Performance Optimized Data Center (POD) 40cp 설치 가이드

다운로드
페이지 21
 
Power management  15 
Standard density HP POD with redundant power 
 
Component 
Quantity  Phases  Amps 
Volts 
Description 
Primary feeders 
225 
415/240 
Supply primary power path to IT 
equipment. 
House power 
feeders 
100 
415/240 
 
One 100A feed to house panel A 
to power HP POD ECS, 
convenience outlet, lighting, and 
auxiliary equipment provided with 
the HP POD. 
 
The second 100A feed supplies an 
alternate source of power to house 
panel B if power path A fails. 
All house panel loads are supplied 
from either house power panel A or B 
through high speed contactors. 
Redundant 
feeders 
225 
415/240 
Supply secondary power path to IT 
equipment. 
 
Either the customer or HP (optional) supplies transformers to convert 3-phase, 480V delta power to 3-
phase, 415V wye power, and switchboards to distribute branch circuit inputs to the HP POD. 
  
 
NOTE:
 For locations outside North America, consult with HP regarding the requirements and 
specifications of transformers. 
  
The customer must supply two 480V, 450A feeders to the transformers that will supply 415V 3-phase 
power to the HP POD. Each power source is capable of supporting the HP POD in the event of a power 
failure or planned maintenance. 
Final connections to the HP POD can be supplied by the customer or by HP at additional cost. 
 
Standard density HP POD without redundancy 
 
Component 
Quantity 
Phases  Amps 
Volts 
Description 
Primary 
feeders 
225 
415/240  Supply primary power path to IT 
equipment 
House power 
feeders 
100 
415/240  House panel A supplies power to HP POD 
ECS, convenience outlet, lighting, and 
auxiliary equipment provided with the HP 
POD. 
Primary 
feeders 
225 
415/240  Supply power path to IT equipment 
 
Either the customer or HP (optional) supplies transformers to convert 3-phase, 480V delta power to 3-
phase, 415V wye power, and switchboards to distribute branch circuit inputs to the HP POD. 
  
 
NOTE:
 For locations outside North America, consult with HP regarding the requirements and 
specifications of transformers. 
  
The customer must supply one 480V, 3-phase, 800A feeder to the transformer that will supply 415V 3 
phase power to the HP POD. 
Final connections to the HP POD can be supplied by the customer or by HP at additional costs.