HP Performance Optimized Data Center (POD) 40cp 설치 가이드
Power management 15
Standard density HP POD with redundant power
Component
Quantity Phases Amps
Volts
Description
Primary feeders
2
3
225
415/240
Supply primary power path to IT
equipment.
equipment.
House power
feeders
feeders
2
3
100
415/240
•
One 100A feed to house panel A
to power HP POD ECS,
convenience outlet, lighting, and
auxiliary equipment provided with
the HP POD.
to power HP POD ECS,
convenience outlet, lighting, and
auxiliary equipment provided with
the HP POD.
•
The second 100A feed supplies an
alternate source of power to house
panel B if power path A fails.
alternate source of power to house
panel B if power path A fails.
All house panel loads are supplied
from either house power panel A or B
through high speed contactors.
from either house power panel A or B
through high speed contactors.
Redundant
feeders
feeders
2
3
225
415/240
Supply secondary power path to IT
equipment.
equipment.
Either the customer or HP (optional) supplies transformers to convert 3-phase, 480V delta power to 3-
phase, 415V wye power, and switchboards to distribute branch circuit inputs to the HP POD.
phase, 415V wye power, and switchboards to distribute branch circuit inputs to the HP POD.
NOTE:
For locations outside North America, consult with HP regarding the requirements and
specifications of transformers.
The customer must supply two 480V, 450A feeders to the transformers that will supply 415V 3-phase
power to the HP POD. Each power source is capable of supporting the HP POD in the event of a power
failure or planned maintenance.
Final connections to the HP POD can be supplied by the customer or by HP at additional cost.
power to the HP POD. Each power source is capable of supporting the HP POD in the event of a power
failure or planned maintenance.
Final connections to the HP POD can be supplied by the customer or by HP at additional cost.
Standard density HP POD without redundancy
Component
Quantity
Phases Amps
Volts
Description
Primary
feeders
feeders
2
3
225
415/240 Supply primary power path to IT
equipment
House power
feeders
feeders
1
3
100
415/240 House panel A supplies power to HP POD
ECS, convenience outlet, lighting, and
auxiliary equipment provided with the HP
POD.
auxiliary equipment provided with the HP
POD.
Primary
feeders
feeders
2
3
225
415/240 Supply power path to IT equipment
Either the customer or HP (optional) supplies transformers to convert 3-phase, 480V delta power to 3-
phase, 415V wye power, and switchboards to distribute branch circuit inputs to the HP POD.
phase, 415V wye power, and switchboards to distribute branch circuit inputs to the HP POD.
NOTE:
For locations outside North America, consult with HP regarding the requirements and
specifications of transformers.
The customer must supply one 480V, 3-phase, 800A feeder to the transformer that will supply 415V 3
phase power to the HP POD.
Final connections to the HP POD can be supplied by the customer or by HP at additional costs.
phase power to the HP POD.
Final connections to the HP POD can be supplied by the customer or by HP at additional costs.