HP Performance Optimized Data Center (POD) 40cp 설치 가이드
Power management 17
Component
Quantity
Phases Amps
Volts
Description
the HP POD.
Primary feeders
3
3
225
415/240
Supply power path to IT equipment.
Either the customer or HP (optional) supplies transformers to convert 3-phase, 480V delta power to 3-
phase, 415V wye power, and switchboards to distribute feeder inputs to the HP POD.
phase, 415V wye power, and switchboards to distribute feeder inputs to the HP POD.
NOTE:
For locations outside North America, consult with HP regarding the requirements and
specifications of transformers.
The customer must supply one 1200A, 480V delta, 3-phase feeder to the transformer that will supply
415V 3 phase power to the HP POD.
Final connections to the HP POD can be supplied by the customer or by HP at additional costs.
415V 3 phase power to the HP POD.
Final connections to the HP POD can be supplied by the customer or by HP at additional costs.
HP POD control power
HP POD control power is supplied by two redundant power house panels that are supplied with:
•
3-phase
•
380 to 415V wye connected
•
50 to 60 Hertz
•
100A
NOTE:
Only one control power panel is required in the non-redundant power path
configuration.
All 3-phase HP POD feeders require that the neutrals and the equipment grounding conductors remain
isolated. Bonding of the two conductors is allowed at the power source only.
isolated. Bonding of the two conductors is allowed at the power source only.