HP Performance Optimized Data Center (POD) 40cp 설치 가이드

다운로드
페이지 21
 
Power management  16 
High density HP POD 
The high density HP POD must be supplied with six feeders. 
• 
3-phase 
• 
380 to 415V wye connected 
• 
50 to 60 Hz 
• 
225A 
Each feeder must contain three phase conductors, one neutral conductor and one equipment ground 
conductor. 
 
High density HP POD with redundant power 
 
Component 
Quantity  Phases  Amps 
Volts 
Description 
Primary feeders 
225 
415/240 
Supply primary power path to IT 
equipment. 
House power 
feeders 
100 
415/240 
 
One 100A feed to house panel A 
to power convenience outlet, 
lighting, and auxiliary equipment 
provided with the HP POD. 
 
The second 100A feed supplies 
an alternate source of power to 
house panel B if power path A 
fails. 
All house panel loads are supplied 
from either house power panel A or B 
through high speed contactors. 
Redundant feeders  3 
225 
415/240 
Supply secondary power path to IT 
equipment. 
 
Either the customer or HP (optional) supplies transformers to convert 3-phase, 480V delta power to 3-
phase, 415V wye power, and switchboards to distribute branch circuit inputs to the HP POD. 
  
 
NOTE:
 For locations outside North America, consult with HP regarding the requirements and 
specifications of transformers. 
  
The customer must supply two 800A, 480V delta, 3-phase feeders to the transformers that will supply 
415V 3 phase power to the HP POD. Each power source is capable of supporting the HP POD in the 
event of a power failure or planned maintenance. 
Final connections to the HP POD can be supplied by the customer or by HP at additional cost. 
 
High density HP POD without redundancy 
 
Component 
Quantity 
Phases  Amps 
Volts 
Description 
Primary feeders 
225 
415/240 
Supply primary power path to IT 
equipment. 
House power 
feeders 
100 
415/240 
House panel A supplies power to HP 
POD ECS, convenience outlet, lighting, 
and auxiliary equipment provided with