Chapter 2 – Applications 
15 
Siemens Industry, Inc. 
BACnet ATEC Owner's Manaul 
125-5050, Rev. AA 
 
4/20/2010 
Calibration 
Air Velocity Sensor 
Calibration of the controller's internal air velocity sensor is periodically required to 
maintain accurate air velocity readings. Calibration may be set to take place 
automatically or manually. 
Autozero Module (AZM) 
Used when damper cannot be closed and constant airflow is needed. 
 
For a controller used with an AZM, calibration occurs without closing the damper. 
Application 6520, 6521, 6522, 6523. 
 
For a controller used without an AZM, the damper is briefly commanded closed to 
get a zero airflow reading and an accurate damper position during calibration. 
Application 6520, 6521, 6522, 6523. 
Hot Water Valve 
Calibration of a hot water valve (if used) is done by briefly commanding the valve 
closed. Application 2863, 2865, 2867. 
Damper Status Operation 
It is possible, after a period of operation, for the calculated damper position to differ 
from the actual (physical) damper position. 
If this occurs, the controller will 
automatically compensate for any difference by 
readjusting the calculated damper position. This calculated position may not match the 
actual position. 
Fail-safe Operation 
If the air velocity sensor fails, the controller uses pressure dependent control. The 
temperature loop controls the operation of the damper. 
If the room temperature sensor fails, then the controller operates using the last known 
temperature value. 
Heating and Cooling Switchover 
The heating/cooling switchover determines whether the controller is in heating or 
cooling mode by monitoring the room temperature and the demand for heating and 
cooling (as determined by the temperature control loops).