Chapter 2 – Applications 
17 
Siemens Industry, Inc. 
BACnet ATEC Owner's Manaul 
125-5050, Rev. AA 
 
4/20/2010 
3.  “Safeties by Others”: This note implies that the associated equipment has safety 
features installed, for example adding mechanical stops to the dampers.  
Application 2860 VAV Cooling Only 
In Application 2860, the controller modulates the supply air damper of the terminal box 
for cooling. In order for it to work properly, the central air-handling unit must provide 
cool supply air. 
See the following figure.  
 
Application 2861 VAV Cooling or Heating 
In Application 2861, the controller modulates the supply air damper of the terminal box 
for cooling and heating. In order for it to work properly, the central air-handling unit 
must provide cool supply air in cooling mode and warm air during heating mode. 
See the following figure.  
 
Application 2862 VAV with Electric Reheat or Baseboard Radiation 
In Application 2862, the controller modulates the supply air damper of the terminal box 
for cooling and controls stages of electric reheat or baseboard radiation for heating. 
When in heating, the terminal box either maintains minimum airflow or modulates the 
supply air damper. In order for the terminal box to work properly, the central air-
handling unit must provide supply air. 
See the following figure.