3.4.2 Internal / External 12V Battery Supply 
For all models there are two terminals provided on the I/O connector designated +12V and GND (or –12V on 
old models). These can be used to power the unit from an external 12V battery or regulated dc supply. For 
the iRIS 320 / iRIS 320V models, the internal battery is effectively connected directly to these terminals. See 
Section 3.4.1 for warnings on connecting external power supplies to them.  
 
 
3.4.3 External (Charger) Power Supply 
Although  the iRIS  320  can  operate solely  from  its  internal  battery  for  a  few  days,  you  will  typically  need  to 
connect  an  external  supply  to  the  unit  so  that  the  internal  battery  remains  in  a  charged  state.    You  can 
connect any external dc power source ranging from 15 – 30Vdc, including a solar panel, without requiring an 
additional solar regulator.   
 
The battery charging circuitry utilises a switch mode regulator for maximum efficiency.  The external power 
supply  is  protected  against  over-voltage  by  ultra-fast  acting  protection  devices  and  a  self-resetting 
semiconductor fuse. 
 
It can also be used to charge an external battery connected to the GND and 12V+ terminals.  In the event 
that  the  external  battery  draws  excessive  current,  the  charger  will  enter  a  current  limit  mode  (900mA)  until 
such  time  as  the  battery  has  been  recharged  sufficiently  to  deliver  the  full  supply  voltage.    The  charging 
profile  used  by  the  charger  depends  on  the  selected  mode.    See  the  Power  Management  description  in 
Section 4.3.1. 
 
 
3.4.4 Analog Inputs 
The four analogue inputs are uni-polar 0-5Vdc with 12-bit resolution.  Each input presents a load impedance 
of 98K
Ω
 to the input signal.  
 
Scaling factors should be chosen to convert from a raw value of 0-5000, which reflects the input signal range 
of 0-5V (0-5000mV).  When current sources such as 0-20mA or 4-20mA are used, an external sink resistor 
(typically 250
Ω
) must be fitted between the analogue input and AGND. 
 
NOTE: As the analogue inputs have an input impedance of 98K
Ω
, the actual sink impedance will be slightly 
lower than the value fitted. For example, a sink resistor of 250 ohms is installed.  The actual impedance will 
theoretically  be  249.36
Ω
;  therefore  the  voltage  measured  by  the  iRIS  will  also  be  slightly  lower  than 
expected.  
 
 
 
 
 
 
 
 
 
 
 
 
 
Figure 5 - Analog Input Circuit 
 
100nF 
47K 
51K 
AGND 
AINx 
To ADC