Optiquest iRIS 220 사용자 설명서

다운로드
페이지 73
 iRIS 220 / iRIS 320, V1.19 User Guide - 16 
 
16
 
iQuest (NZ) Ltd  - PO Box 15169, Hamilton, New Zealand  Tel: +64 7 857-0810  Fax: +64 7 857-0811  Email: iquest@iquest.co.nz
 
 
 
3.4.5 Digital Inputs 
The two digital inputs are jumper selectable for either mechanical or electronic operation.  In either case it is 
necessary  to  pull  the  input  down  to  0Vdc  to  activate  it.    Inputs  will  handle  up  to  30Vdc  in  the  off  state  for 
parallel  connection  across  existing  equipment.    Jumpers  are  positioned  to  the  right  hand  side  of  the  I/O 
connector.  The top jumper is for Digital Input #2 and the bottom jumper is for Digital Input #1. 
 
Fit the jumper for mechanical switching at up to 100Hz.  In this mode the input is normally pulled up to 12V 
through a 10K
Ω
 resistor providing a wetting current of approximately 1.6mA.  A 100nF capacitor is also fitted 
across  the  input  to  provide  limited  hardware  debounce,  preventing  false  triggering  due  to  contact  bounce.  
For installations that do not have an external power source it is important that the input is not held low for a 
prolonged period of time, as this will increase the current drawn from the internal battery. 
 
Remove  the  appropriate  jumper  for  electronic  switching  at  up  to  5kHz.    In  this  mode  the  input  is  normally 
pulled up to 3.6V through a 57K
Ω
 resistance, providing a wetting current of approximately 60
µ
A. 
 
 
 
 
 
 
 
 
 
 
 
 
Figure 6 - Digital Input Circuit 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
IMPORTANT NOTE! 
 
In  almost  all  installations  where  an  iRIS  is  connected  in  parallel  with  other  equipment  to  share  a 
common  pulse  input  (e.g.  from  a  flow  meter),  there  has  not  been  a  detrimental  effect,  as  the  iRIS 
inputs  present  a  relatively  high  impedance  to  the  circuit.    However,  in  the  event  that  connecting  an 
iRIS  does  cause  pulse  failure,  iQuest  recommend  removing  the  debounce  selection  link  for  the 
appropriate input.  This sets the input to electronic switching mode, even if the actual pulse source is 
a clean contact (reed switch or similar).  
 
The  debounce  jumpers  are  located  very  close  to  the  right-hand  side  of  the  I/O  connector  and  are 
therefore not normally visible. To gain access to the jumpers, follow this procedure:  
 
iRIS 220. Remove the electronic assembly from the case.  See Section 3.1 
 
iRIS  320  /  iRIS  320V.  Unplug  the  green  I/O  connector  and  then  undo  the  two  hinge  screws 
completely, so that the enclosure lid can be lifted off.  See Section 3.2 
 
Fit or remove the jumpers(s) as required, then reverse the procedure to reassemble the unit. 
Hint: If removing a jumper, simply fit it to one pin only of the connector to avoid it being lost. 
 
 
 
DINx 
DGND 
100nF 
JPx 
4K7 
10K 
+12V 
3V6 
1nF 
47K 
To internal logic circuitry