3.4 I/O Connector 
All  I/O  and  power  supply  terminations  are  via  5mm  (0.2”) screw  terminals provided  on  a  16-way  pluggable 
connector.    The  older  (V1.1)  PCB  has  a  12  way  connector  -  see  Appendix  D  –  Legacy  PCB  (Rev  1.1) 
Details. The I/O connector is positioned on the right hand side of the iRIS 320 circuit board, directly above 
the white battery connector.  On the iRIS 220, the connector protrudes through the top of the case. 
 
The function of each I/O termination is shown in the diagram below. 
 
TOP 
 
AI4 
 Analog Input #4 
AI3 
 Analog Input #3 
AI2 
 Analog Input #2 
AI1 
 Analog Input #1 
AGND   Analog Common Ground 
5VOP   5V Reference Output 
DI2 
 Digital Input #2 
DI1 
 Digital Input #1 
DO2 
 Digital Output #2 
DO1 
 Digital Output #1 
SDI-12   SDI-12 Data Bus 
DGND   Digital Common Ground 
12V+ 
 12Vdc Internal/External Battery Supply + 
GND (-)  0Vdc Internal/External Battery Supply - 
VIN+ 
 15-30Vdc External Power Supply (Charger Input) + 
GND (-)  0Vdc External Power Supply (Charger Input) - 
 
BOTTOM 
Figure 4 - I/O Connector 
 
3.4.1 Internal Battery (iRIS 320 / iRIS 320V only) 
The iRIS 320 / iRIS 320V are supplied with an internal rechargeable 12V 0.8A/Hr sealed lead-acid battery.  
Upon installation, you will need to connect this battery as it is shipped disconnected to preserve battery life. It 
should also be disconnected if the unit is not going to be used for some time. 
  
NOTE:  The iRIS 220 does not have an internal battery, so ignore all references to the internal battery 
for the iRIS 220 models. 
 
 
For maximum flexibility, the iRIS I/O connector has two terminals provided for additional 12V power supply 
flexibility.  These  terminals  (marked  12V+  and  GND)  can  either  be  used  to  deliver  12V  from  the  internal 
battery out to power an external sensor or other small load, or alternatively be connected to an external 12V 
battery  (for  greater  battery  capacity)  or  a  12V  d.c  battery  charger  type  power  supply.    See  the  next  two 
sections on using the 12V terminals and the external (charger) power supply feature. 
 
 
 
 
 
 
 
 
 
 
 
 
 
WARNING!  
iRIS 320 / iRIS 320V INTERNAL BATTERY 
 
The +12V and GND terminals of the I/O connector are effectively connected directly in parallel with 
the internal 12V battery.  A resettable semiconductor fuse is fitted for short-circuit protection.  
 
However,  only  connect  12V  lead-acid  batteries  or  a  regulated  d.c  power  supply  that  is  designed 
for charging a 12V lead-acid battery, to these terminals.  
 
Applying  a  voltage  higher  than  14.5V  for  a  sustained  period  to  these  terminals  will  permanently 
damage the internal battery and may cause an acid leak and/or an explosion.