Siemens REV23 사용자 설명서

다운로드
페이지 12
4/12
Siemens Building Technologies
Room Temperature Controller REV23
CE1N2264en
HVAC Products
23.04.2002
Setpoint economy mode
remote operation
10 °C
30 °C
Time switch
Main menu
Submenu
Settings
Selection of day of week, working
day, weekend or week
Selection of the number of heating
or cooling periods, max. 3
Selection of heating / cooling period start and end time
° C
T
Selection of heating / cooling period setpoint temperature
Absence
Main menu
Submenu
Entry of holidays or periods of absence.
(number of days with economy mode setting /
max. 99 days)
Temperature setpoint during absence
Factory setting 12 °C
Menu-driven heating
engineer settings
Main menu
Settings
CAL
Sensor calibration
Setpoint limitation
Optimum start control for first heating period
(in unit of time per 1 °C)
2-position control
PID mode, self-learning
PID mode with a switching cycle of 6 or
12 minutes
  
/
  
Periodic pump run Off / On
Operating mode heating / cooling
In the automatic operating modes, temperature setpoints can be individually adjusted
for every comfort period and for the continuous operating modes. The temperature
setpoint of economy mode is the same in automatic and continuous operation.
In the frost or overtemperature protection mode, the room temperature is constantly
monitored. If it falls (rises) below (above) the adjusted setpoint, heating / cooling is
switched on to maintain the adjusted frost or overtemperature protection setpoint tem-
perature 
 .
Temperature
setpoints
Protective function