2.6  Installation of Optional Modules
CAUTION: Remove all power (AC and DC) before installing or removing modules or 
wiring.
2.6.1  CAC-4 Class A Converter Module (MS-4 only)
2.6.1.1  Installation
The CAC-4 Module can be used to convert the four Style B (Class B) Initiating 
Device Circuits to Style D (Class A) and the two Style Y (Class B) Notification 
Appliance Circuits to Style Z (Class A).  The module plugs into connector J1 which 
is located at the top right of the MS-4 main circuit board.
Install the three supplied standoffs in the holes on the main circuit board as 
indicated in the following figure.  Carefully align the connector on the CAC-4 with 
J1 on the FACP main circuit board and press the module securely into place.  Make 
certain the pins are properly aligned to prevent bending or breaking of any 
connector pins.  