Honeywell 800-04433V1 Manual Do Utilizador
iPGSM-COM Commercial Fire Communicator – Installation and Setup Guide
– 8 –
Dialer Capture Module Information
LED Indicator
STATUS
RED – Steady ON
Messages exist in buffer.
RED – Flashing
No messages to be sent. Waiting for messages.
GREEN – Steady ON
Normal Indication.
GREEN – Blinks every 2 sec.
PowerBoost1 communication problem.
GREEN – Blinks twice every sec.
Communication Module connection is lost.
GREEN – Blinks 10 times every sec.
PowerBoost1 and Communications Module connection is lost.
iPGSM-COM-004-V0
Dialer Capture Module
Telco 1
Telco 2
ECP
Tip 2
Ring 2
ZN-
EOL
EOL
ZN+
PWR
GND
Tip 1
Ring 1
Data Out
Data In
12V In
GND
RED
GREEN
LED Board Information
Panel Status
LED Indicator
RADIO TROUBLE
Yellow – ON when radio trouble is present.
Buzzer – Upon loss of AC power, this will
beep once every 10 seconds.
beep once every 10 seconds.
LOW BATTERY
Yellow – ON when battery is low.
Yellow – (not used)
AC LOSS
Yellow – ON when no AC is present.
AC ON
Green – ON when AC is present.
Note: Telco ports 1 (primary dialer)
and 2 (secondary dialer) may be
used instead of the terminal board.
Whichever connection method is
used instead of the terminal board.
Whichever connection method is
used, both Telco paths must be
connected to the Fire Panel.
iPGSM-COM-006-V0
Buzzer