iPGSM-COM Commercial Fire Communicator – Installation and Setup Guide
 
 
– 6 – 
STEP 5 – Program the Communications Module 
You must use the 7720P Programming tool to program the iPGSM-COM.  
When using the 7720P Programming tool, the values given below are for most installations.  Press the [#] 
key to accept the displayed default value (xxx) or enter the new value and press the [#] key for the next 
prompt.  Use the [
] key to scroll through a list of options. 
 
 
 
1.    (no display) 
Connect the 7720P. 
 
 
 
2.  7720P PROGRAMMER 
Press [#]. 
 
 
 
3.  Strt Prog Mode? Y/N 
Press [Shift] then [Y], then [#]. 
 
 
 
4.  Program Device?  Y/N  
Press [Shift] then [Y], then [#].   
 
 
 
5.  Primary City ID  (??) 
Enter number 01-99, then press [#]. 
 
 
 
6.  Primary CS ID  (??)  
Enter number 01-FE, then press [#]. 
 
 
 
7.  Primary Sub ID  (????)  
Enter number 0001-9999, then press [#].  
 
 
 
8.  Review? Y/N 
Enter choice, then press [#].  Follow the prompts. 
 
 
 
9.  Create Password?  Y/N 
Enter choice, then press [#].  Follow the prompts. 
 
 
 
10.  Exit Prog Mode? Y/N 
Press [Shift] then [Y], then press [#]. 
 
 
 
11.  DONE 
 
 
 
 
Note: If an error in programming occurs, set the factory defaults (see next topic) and 
reprogram the iPGSM-COM. 
To exit the programming mode, press [N] in response to the "Review?" prompt.  Then press [Y] to the "Exit 
Prog Mode?" prompt.  Upon exiting, the root file is updated to log the changes made.  A message is displayed 
telling the user that this step is being executed.  When complete, the message "DONE" is displayed to 
indicate the file was successfully uploaded. 
Note: If critical configuration changes were made, such as the mode of operation, the 
communications module will reset to ensure that the programming features are enabled. 
If the file is not successfully uploaded, one of the following prompts will be displayed.  Follow the steps 
shown below until the upload is successful. 
Display 
Description 
What to do 
Cannot Upload 
Try Again?   Y/N_  
Module is not yet initialized. 
Wait for RSSI indicator LEDs to be lit.  
Press [Y]. 
Failed to Update 
Root File! 
Network problem, or you 
answered "N" to "Cannot 
Upload Try Again?" prompt. 
Initiate the Force Server Update 
Command by pressing the [0] key. 
 
Setting Factory Defaults
 
To reset the programming options to factory-default values, at the "Exit Prog Mode?" prompt press [Shift] 
plus [ESC].  Note, setting the factory defaults will also erase any password that may have been entered. 
 
Set Default? 
Y/N_
  
Press [Y] to reset factory default values. 
Press [N] to cancel this function.
 
 
Press [Shift] then [Y], then [#].  The Create Password prompt appears, follow the prompts then exit.