iPGSM-COM Commercial Fire Communicator – Installation and Setup Guide 
 
– 7 – 
STEP 6 – Configure the Fire Panel 
1.  Ensure the Telco Fault on the panel is enabled.  Then choose a setting that is no higher than 90 
seconds (or as close to that) as the panel allows. 
2.  Ensure no more than 1 pause character (usually a comma) is programmed into the dialing string 
(usually 2 seconds).  Note, this is necessary since the Dialer Capture Module waits only 3 seconds 
after the phone number is dialed.  Having more than 3 seconds of pause time will cause it to think 
the phone number is complete and cause it to generate the high-low tones at an incorrect moment. 
 
STEP 7 – Test the System 
1.  Close the Wall Outlet Box, then close and lock the cabinet cover.  
2.  Refer to the fire panel's installation/operation  guide the testing procedure. 
3.  (Notify the monitoring station that a test will be conducted.)  Test the system to ensure it is 
operating. 
 
iPGSM-COM Trouble Detection Information 
Telco 1 is used for the Fire Panel to output contact ID messages to the iPGSM-COM, and Telco 2 is used by 
the iPGSM-COM to report faults to the Fire Panel.  If Telco 1 is not operational, the Fire Panel will use 
Telco 2 to report events if there are no faults in the iGSM Communications module.  
Fault Condition 
Indication to Fire Panel 
PowerBoost1 fault 
Telco 2 is cut.  
iGSM Communications Module fault 
 
  Failure of one of the two 
communications paths. 
Telco 2 is cut. 
  Failure of both communications 
paths. 
Telco 1 and 2 are cut. 
Dialer Capture Module buffer is full. 
Hang up.  (Panel will retry, giving the buffer a chance to empty.)