Honeywell IPGSM-4GC Manual Do Utilizador

Página de 24
IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide 
 
– 9 – 
Dialer Capture Module Information 
 
LED Indicator 
STATUS 
RED – Steady ON 
Messages exist in buffer. 
RED – Flashing 
No messages to be sent.  Waiting for messages. 
GREEN – Steady ON 
Normal Indication. 
GREEN – Blinks every 2 sec. 
PowerBoost1 communication problem. 
GREEN – Blinks twice every sec. 
Connection with the Communicator is lost. 
GREEN – Blinks 10 times every sec. 
PowerBoost1 and Communicator connections are lost. 
 
 
iPGSM-COM-004-V0
Dialer Capture Module
Telco 1
Telco 2
ECP
Tip 2
Ring 2
ZN-
EOL
EOL
ZN+
P
W
R
GND
Tip 1
Ring 1
Data O
u
t
Data In
12V  In
GND
RED
GREEN
 
 
 
LED Display Information 
 
Status LED 
Indicator 
RADIO TROUBLE 
Yellow – ON when radio trouble is present. 
 
Both IP and GSM communication paths are lost. 
 
Communicator radio is not registered. 
 
Old Alarm Time has been exceeded.  (Message has not been 
delivered within the fixed 10 minute window.)  
 
Buzzer – Upon loss of AC power, this will beep once every 10 
seconds.  
LOW BATTERY 
Yellow – ON when battery is low (<11.5VDC). 
 
Yellow – (not used)   
AC LOSS 
Yellow – ON when no AC is present (< 90VAC).   
AC ON 
Green – ON when AC is present. 
 
Note: If a wire pulled out of the LED Board Connector  
refer to the diagram on right and reinsert wire, ensuring  
the connector pin is locked in. 
 
 
 
Note: Telco ports 1 (primary dialer) 
and 2 (secondary dialer) may be used 
instead of the terminal board. 
Whichever connection method is used, 
both Telco paths must be connected to 
the Fire Panel.  
NC
NC
LED Board 
Connector
Wires
Violet
Black
White
Red
Brown
Yellow
Gray
b
u
zzer
RADIO TROUBLE
LOW BATTERY
AC ON
(not used)
AC LOSS