IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide
– 6 –
Wiring the 659EN Line Fault Monitor (Required for ULC)
The IPGSM-4GC is compatible with Fire Panels when the model 659EN Line Fault Monitor, (also known as the HFS-
659EN), is installed. Note, the wire colors may vary.
659EN), is installed. Note, the wire colors may vary.
1. Refer to the installation guide for the 659EN.
2. Mount the 659EN on the lower left side of the IPGSM-4GC cabinet.
3. DO NOT cut the 659EN’s BLACK Output Relay Jumper or the BLUE Voltage Trip Threshold Jumper.
4. Complete the interface wiring as shown below:
to Dialer Capture Module, Terminal, Tip 2
to Dialer Capture Module, Terminal, Ring 2
to Power Boost 1, Terminal, OUTPUT 1, DC+
to Power Boost 1, Terminal, OUTPUT 1, DC-
to Power Boost 1, Terminal, ERTH GND
Wire to a
Zone on the Fire Panel
Zone on the Fire Panel
659EN
YEL
ORG
RED
BLK
GRN
IPGSM-4GC-013-
V
0
4.7K, 1/2 watt
IPGSM-4GC
Example wiring for an addressable fire control panel:
T11
T10
T9
T8
T7
T6
T10
T9
T8
T7
T6
T1
T2
T3
T4
T5
T2
T3
T4
T5
1 0
2
3
4
5
6 7 8 9
10
11
12
13
14
15
1 0
2
3
4
5
6 7 8 9
TENS
ONES
LOOP
ADDRESS
TOP
B+ A+ B- A- A B
NO NC C
TB2
TB5
SLC Loop
FIRE LITE Addressable Fire Alarm Control Panel
MS-9050UD
MS-9050UD
MMF-300A
Monitor Module
- To next device
+ on SLC Loop
+ on SLC Loop
Braided-shield/Drain
Wire
Wire
RELAY 1
ALARM CONTACTS
IPGSM-4GC
Commercial Fire Communicator
Commercial Fire Communicator
to Dialer Capture Module, Terminal, Tip 2
to Dialer Capture Module, Terminal, Ring 2
to Power Boost 1, Terminal, OUTPUT 1, DC+
to Power Boost 1, Terminal, OUTPUT 1, DC-
to Power Boost 1, Terminal, ERTH GND
659EN
YEL
ORG
RED
BLK
GRN
47K, 1/2 watt
B+
B-
Shield
IPGSM-4GC-014-V0