Honeywell IPGSM-4GC Manual Do Utilizador

Página de 24
IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide
 
 
– 8 – 
To exit the programming mode, press [N] in response to the "Review?" prompt.  Then press [Y] to the "Exit Prog 
Mode?" prompt.  Upon exiting, the root file is updated to log the changes made.  A message is displayed telling the 
user that this step is being executed.  When complete, the message "DONE" is displayed to indicate the file was 
successfully uploaded. 
Note: If critical configuration changes were made, such as the mode of operation, the communicator 
will reset to ensure that the programming features are enabled. 
If the file is not successfully uploaded, one of the following prompts will be displayed.  Follow the steps shown below 
until the upload is successful. 
Display 
Description 
What to do 
Cannot Upload 
Try Again?   Y/N_ 
 
Communicator is not yet initialized. 
Wait for RSSI indicator LEDs to be lit.  
Press [Y]. 
Failed to Update 
Root File!
 
Network problem, or you answered "N" to 
"Cannot Upload Try Again?" prompt. 
Initiate the Force Server Update 
Command by pressing the [0] key. 
 
Setting Factory Defaults 
To reset the programming options to factory-default values, at the "Exit Prog Mode?" prompt press [Shift] plus [ESC].  
Note, setting the factory defaults will also erase any password that may have been entered. 
Set Default? 
Y/N_  
Press [Y] to reset factory default values. 
Press [N] to cancel this function.
 
 
Press [Shift] then [Y], then [#].  The Create Password prompt appears, follow the prompts then exit.  
 
STEP 6 – Configure the Fire Panel 
1.  Ensure the Phone Line Supervision (or Telco Fault) on the panel is enabled.  Then choose a setting that is no 
higher than 90 seconds (or as close to that as the panel allows). 
2.  Ensure no more than 1 pause character (usually a comma) is programmed into the dialing string (usually 2 
seconds).  Note, this is necessary since the Dialer Capture Module waits only 3 seconds after the phone 
number is dialed.  Having more than 3 seconds of pause time will cause it to think the phone number is 
complete and cause it to generate the high-low tones at an incorrect moment. 
 
STEP 7 – Test the System 
1.  Close the 1451-UL9 Wired Transformer enclosure, then close and lock the cabinet cover.  
2.  Refer to the fire panel's installation/operation guide for the testing procedure. 
3.  (Notify the monitoring station that a test will be conducted.)  Test the system to ensure it is operating. 
4.  Verify communications with the monitoring station is successful by sending several events.  Also, get 
confirmation that these events were received.