HA40 4-Channel Controller
Revision 1 (07/08)
HA40 Technical Manual
2-4
2�2�3 Fault / Alarm 1 / Alarm 2 / Alarm 3 Set-Up Menus
Alarm 12 and 3 have identical menus.  The only difference between 
each is that A1 front panel LED indicators are yellow while A2 and A3 
are red.  Typical applications often have A1 set at a WARN level, A2 
at a HIGH level and A3 at a higher SHUT DOWN level.  However, it 
is important to understand there is no functional difference between 
A1, A2 and A3 (since their configuration menus are identical, only 
one is shown in Figure 2-19).  The 
Fault menu is identical to A1, A2, 
A3 except Fault alarms are always low trips (alarm activates as input 
goes below the set point) and Fault alarms may not be set for latching 
operation.
Figure 2-3. Alarm/Fault Setup Menu
Set  Point
  is  entered  in  engineering  units  and  determines 
the value at which the alarm trips.  For example, if a channel 
monitors 0-50 ppm H
2
S and the desired alarm level is 10 ppm, 
the correct entry is 10.00.  A one percent dead band prevents 
alarm chatter.  This means after tripping an alarm the input must 
move at least 1% of full scale back through the setpoint for the 
alarm to auto reset.
The 
• 
ON Delay / OFF Delay entries allow ON and OFF time 
delays  affecting  how  long  the  trip-point  must  be  surpassed 
before an alarm event transition occurs.  ON delays are limited 
to  10  seconds  while  OFF  delays  may  be  as  long  as  120 
minutes.    Delays  are  useful  in  many  applications  to  prevent 
nuisance alarms and unwanted cycling into and out of alarm 
conditions.
Low Trip
 is set for NO to increase alarms or YES to decrease 
alarms to determine if the alarm activates upon exceeding or 
falling below the set-point.
Latching
 determines either manual or automatic alarm reset 
operation.  YES requires a manual Alarm Reset to unlatch the 
alarm even though an alarm condition no longer exists.  YES 
also causes this alarm’s common relay, front panel LED, and 
optional discrete relay to latch.  NO allows all outputs for this 
alarm to automatically reset after the alarm condition clears.
Common  alarm  LED  indicators  on  the  left  side  of  the  front  panel 
indicate the status of A1, A2 A3 alarms.  The common Fault LED is on 
the lower right side of the front panel.  Any new alarm event causes 
the  associated  LED  to  flash  until  an  Alarm  Reset  occurs  causing 
an acknowledged steady on condition.  Operators should recognize 
new alarms by a flashing LED.  Alarm Reset also acknowledges, or 
deactivates, audible devices driven by the AUDIBLE ALARM option 
connector J2 (see 
Figure 3.2
)
2�2�4 Configure Menu To Define Channel
The next menu option, after the Alarm menu, is Configure.  It allows 
setting Name and EUNIT 10 digit ASCII fields, defines the measurement 
range  with  ZERO  &  SPAN  entries,  number  of  Decimal  Points  of 
resolution the reading will have, and if the channel is Active.
Figure 2-4. Configure Menu to Define Channel