Honeywell HA40 Manual Do Utilizador

Página de 39
HA40 4-Channel Controller
Revision 1 (07/08)
HA40 Technical Manual
2-5
Name / Eunits ASCII Data Fields
The  first  two  items  in  this  menu  are  for  entering  the  10  character 
channel  Name  and  engineering  unit  ASCII  fields.    Name  should 
describe the channel’s data in user terminology such as tag # or other 
description.  Eunits should define the units of measure for what this 
channel is to display.  Section 2.6 describes how to modify these fields 
using the keypad.
Input Measurement Range
The 
Zero / Span menu options allow configuration of the measurement 
range  displayed  by  this  channel.    Measurement  Range  defines 
the range of the input signal’s engineering units.  For example, if a 
channel’s input is 4-20mA from a transmitter monitoring 0 to 10ppm 
chlorine, then the Zero value should equal 0.000 and the Span value 
equal 10.00.  Four digits must be entered so trailing 0’s may appear 
here  that  are  not  displayed  on  other  data  screens.   These  menus 
work hand in hand with the Min/Max Raw Counts menus described 
in section 2.7.4.
Decimal Point Resolution
Resolution of the displayed channel value is configured in the 
Decimal 
Pts� menu by setting the number of digits trailing the decimal point.  
Displayed  readings  are  limited  to  a  maximum  of  four  digits  with  a 
polarity sign.  Auto-ranging displays the highest resolution allowed by 
this menu’s decimal point entry.  For example, a range of 0 to 100ppm 
and two decimal points reads 0.00 at 0ppm and 100.0 at 100ppm.  
This may be undesirable due to the high resolution at zero unless the 
sensor’s output is extremely stable.  If decimal points are limited to 
one, the 0ppm reading becomes 0.0 and the 100ppm reading remains 
100.0.  Resolution may be limited further by setting decimal points to 0 
where in the above example, 0ppm reads 0 and 100ppm reads 100.
Turning Off Unused Channels
The 
Channel Active menu option asks if this channel is to be utilized.  
NO  causes  the  controller  to  never  process  inputs  applied  to  this 
channel and no alarms are tripped or data displayed.  Inactive channels 
have a line drawn through them on the Setup screen to indicate they 
are turned off.