3-4
3�1�2 Optional Analog Input PCB
(P/N 10-0221)
Transmitter  input  PCB  option  #  10-0298,  shown  in  Figure  3-3,  is 
available for interfacing the HA40 to field transmitters with 4-20mA or 
voltage outputs (0-2 VDC max).  TB1 & TB2 provide Channel 24VDC, 
HI and LO terminals for receiving analog inputs.  R1, R2, R3, & R4 are 
100 ohm precision socketed termination resistors connected between 
each channel’s HI & LO input terminals.  These may be removed if 
voltage inputs are to be applied.  Figure 3-4 shows correct wiring for 
both 2-wire and 3-wire transmitters.
TB3 provides the dedicated failsafe-5 amp-form C common FAULT 
relay.  
Figure 3-3. Optional Analog Input PCB (P/N 10-0221)
Figure 3-4. Wiring for 2- and 3-wire Transmitters
3�1�3 Optional Discrete Relay PCB’s
(P/N 10-0222)
The optional Discrete Relay PCB, shown in Figure 3-5, adds six 5 
amp form C relays.  Each relay is fully programmable as described in 
Section 2.3.1
.  Many HA40 applications utilize the standard equipped 
Relay  1  /  Relay  2  (see 
Section  2.3.1
)  and  do  not  require  optional 
discrete relays 
Warning
All mechanical (dry contact) relays are rated at 5 Amp for 28 VDC 
and 250 ~VAC RESISTIVE loads.  IMPORTANT:  Appropriate diode (DC 
loads) or MOV (AC loads) snubber devices must be installed with 
inductive loads to prevent RFI noise spikes.  
AC or DC power supplies to relays on the 10-0222 Discrete Relay PCB 
option must be the same for each relay.  Example:  24VDC should not 