HA40 4-Channel Controller
Revision 1 (08/08)
HA40 Technical Manual
3-5
K1, K2, K3, K4, K5 & K6 are 
programmable, as described 
in section 2.3.1
Figure 3-5. Optional Discrete Relay PCB’s (P/N 10-0222)
3�1�4 Optional 4-20mA Analog Output Board
(P/N 10-0308)
An optional 4-20mA analog output board, shown in Figure 3-6, may 
be added.  Each channel’s output will transmit 4mA for 0% readings 
and 20mA for 100% readings.  
Make certain that the mA loop output is 
set to LATCHING on reading devices connected to the HA40. 
If the HA40 primary power is 100 – 240 VAC, 4-20mA outputs are 
capable of driving 20mA through a 750 ohm load.  Outputs are self 
powered and DC power should not be provided by the receiving device.  
Precision  calibration  of  the  4-20mA  output  DAC  (digital  to  analog 
converter) is accomplished via the Analog Setup menu as described 
in 
Section 2.3.4
.
1
2
3
4
1
2
3
4
4-20mA OUTPUTS
CH1
CH2
CH3
CH4
+      -
+      -
+      -
+      -
TB1
TB2
TB1
Assy # 10-0308
4-20mA Outputs are sourcing and 
24 VDC power must not be supplied by 
the receiver device
Loop Drive capability is 750 ohms with 
nominal 85-240 VAC power or 24 VDC 
power as the Controller primary power 
supply.
Make certain that the mA loop 
output is set to LATCHING on reading 
devices connected to the HA40.
Optional 4-20mA Outputs Notes
Figure 3-6. Optional Optional 4-20mA Analog Output Board (P/N 10-0308)