InRow RC Installation
22
Electrical Connections
The following electrical connections are required in the field:
• Feeds A and B
• A-Link
• Network Management Card
• Temperature sensor
• Communication (building management system)
See the electrical schematic (located on the lid of the electrical box) for all electrical 
connections.
Make all electrical connections in accordance with national and local codes.
See the InRow RC nameplate for voltage and current requirements.
A power disconnect is required to isolate each InRow RC for maintenance and service.
All low-voltage connections, including data and control connections, must be made with properly 
insulated wires. The low-voltage connections must have 300-V minimum insulation.
Note: Single phase service is required. Electrical service must conform to national and local 
electrical codes. The InRow RC is grounded through the power cord.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Turn off all power supplying this equipment before working on the equipment.
• Use a voltmeter to ensure that power is turned off before making any electrical 
connections.
Failure to follow these instructions will result in death or serious injury.