APC ACRC103 Manual Do Utilizador

Página de 36
23
InRow RC Installation
Power connections
Power cords may be routed through the top of the equipment (standard) or through the bottom (optional).
Top wiring configuration 
(standard). 
1. Route power cords 
through the 
equipment to the top 
power cord access, 
as shown.
2. Push the power cords 
through the hole at 
the top power cord 
entrance.
3. Secure the plate to 
the underside of the 
equipment top with 
four Phillips screws 
(provided).
4. Secure the power 
cords at appropriate 
locations inside the 
equipment using the 
provided tie wraps.
Bottom wiring configuration (optional). 
1. Remove the blank plate from the bottom power cord entrance. Save the plate and the four Torx 
screws.
2. Route the power cords through the equipment to the bottom power cord access, as shown.
3. Feed the power cords through the hole at the bottom power cord entrance and secure the plate to 
the bottom of the equipment with the four Torx screws you saved in step 1.
4. Secure the blank plate to the top power entrance with four Phillips screws (provided).
5. Secure the power cords at appropriate locations inside the equipment using the provided wire 
ties.
Feeds A and B. 
The equipment is capable of receiving power through one of two separate feeds, feed 
A or feed B. Use the display interface to configure the unit to receive power through feed A, feed B, or 
both). If connected, feed B is the primary power input to the equipment by default; feed A is the backup 
power input. The equipment receives power through feed B regardless of whether feed A is receiving 
power. If power is removed from feed B, feed A takes over and supplies power to the equipment (if feed 
A is connected). Connect the feed A and feed B cables to individual, breaker-controlled branch circuits 
or to PDUs backed by separate Uninterruptible Power Supplies (UPS).
Note: Feed A and feed B must not use the same branch circuit, PDU, or UPS.
For more information on configuring power input feeds, see the InRow RC Operation and 
Maintenance
 manual.
na
15
81a
Plate
Bottom power entrance
Screws
Top power 
cord entrance