APC AP7900 Manual Do Utilizador

Página de 186
®
USER’S GUIDE
Switched Rack PDU
43
Control actions you can select. 
t
Option
Description
No Action (Web interface only)
Do nothing.
On Immediate
Apply power to the selected outlets.
On Delayed
Apply power to each selected outlet according to its 
value for 
Power On Delay
.
 
Off Immediate
Remove power from the selected outlets.
Off Delayed
Remove power from each selected outlet according to 
its value for 
Power Off Delay
.
Reboot Immediate
Remove power from each selected outlet. Then apply 
power to each of these outlets according to its value 
for 
Reboot Duration
.
Reboot Delayed
Remove power from each selected outlet according to 
its value for 
Power Off Delay
. Wait until all outlets are 
off (the highest value for 
Reboot Duration
), and then 
apply power to each outlet according to its value for 
Power On Delay
Cancel Pending Commands 
(Web Interface)
Cancel (control console)
Cancel all commands pending for the selected outlets 
and keep them in their present state.
N
OTE
:
For global outlet groups, you can cancel a 
command only from the interface of the initiator outlet 
group. The action will cancel the command for the 
initiator outlet group and all follower outlet groups.
† If a local outlet group is selected, only the configured delays and reboot duration of the lowest-
numbered outlet of the group are used. If a global outlet group is selected, only the configured 