APC AP7900 Manual Do Utilizador

Página de 186
®
USER’S GUIDE
Switched Rack PDU
44
How to configure outlet settings and outlet name
Settings that you can configure. 
The following settings are available in 
both the Web interface and control console unless otherwise indicated:
Setting
Description
Power On Delay
Set the number of seconds that the Rack PDU waits after a 
command is issued before applying power to an outlet.
N
OTE
:
To configure an outlet to remain off at all times, check the 
Never
 check box next to 
Power On Delay
 in the Web interface, or 
configure a value of 
–1
 for 
Power On Delay
 in the control console. 
Power Off Delay
Set the number of seconds that the Rack PDU waits after a 
command is issued before removing power from an outlet.
N
OTE
:
To configure an outlet to remain on at all times, check the 
Never
 check box next to 
Power Off Delay
 in the Web interface, or 
configure a value of 
–1
 for 
Power Off Delay
 in the control console. 
Reboot Duration
Set the number of seconds an outlet remains off before restarting.
Name (Web 
interface)
Outlet Name 
(control console)
Set the name for one or more outlets. The name is displayed next 
to the outlet number on status screens.
Link (Web 
interface)
Define an HTTP or HTTPS link to a Web site or IP address.
 links the outlet to the home page of the 
APC Web site. 
http://158.205.7.201
 links the outlet to the Web interface of the 
Switched Rack PDU at the IP address 158.205.7.201, enabling 
you to log on to that interface (if you have the appropriate access).
N
OTE
:
If the outlet is a member of an outlet group, the only link that 
is used is the link configured for the global outlet or (for a local 
outlet group) the link configured for the lowest-numbered outlet of a 
local outlet group. You can configure a link for another outlet in an 
outlet group, but that link will be available to use only when that 
outlet is no longer a member of an outlet group.