APC AP7900 Manual Do Utilizador

Página de 186
®
USER’S GUIDE
Switched Rack PDU
75
Rack PDU will add this domain name when only a hostname is 
entered.
• A
 Port Speed
 setting is available for all 
Boot mode
 selections to 
define the TCP/IP port’s communication speed (
Auto-negotiate
, by 
default).
• Three settings are available for all 
Boot mode
 selections, except 
Manual
, to identify the Rack PDU in BOOTP or DHCP communication:
Vendor Class
: Uses 
APC
, by default.
Client ID
: Uses the Rack PDU’s MAC address, by default.
User Class
: Uses the Rack PDU’s application module type, by 
default. 
• Two settings are available if 
BOOTP only
 is the Boot mode selection:
Retry Then Fail
: Defines how many times the Rack PDU will 
attempt to discover a BOOTP server before it stops (4, by default).
To override the expansion of a specified host name by the 
addition of the domain name, do one of the following:
• To override the behavior in all instances, set the 
domain name field in 
Configure General Settings
 to 
its default 
somedomain.com
 or to 
0.0.0.0
.
• To override the behavior for a particular host name 
entry — for example when defining a trap receiver — 
include a trailing period. The Switched Rack PDU 
recognizes a host name with a trailing period (such as 
mySnmpServer.
) as if it were a fully qualified domain 
name and therefore does not append the domain 
name.
Caution
If the 
Client ID 
is changed from the Rack PDU’s MAC 
address, the new value must be unique on the LAN. 
Otherwise, the DHCP or BOOTP server may act incorrectly.