APC AP7900 Manual Do Utilizador
®
USER’S GUIDE
Switched Rack PDU
46
Switched Rack PDU Settings
Configure Load Thresholds
Web interface.
1. Select
Switched Rack PDU
from the navigation menu.
2. Click
Configure
in the
Load Management
section.
3. Set
Overload Alarm Threshold
,
Near Overload Warning Threshold
,
Low Load Warning
Threshold
, and
Overload Outlet Restrictions
for each phase or bank.
4. Click
Apply
in that section to set the selected values.
Control console.
1. From the
Device Manager
menu, select
Phase/Bank Monitor/
Configuration
.
2. Select a phase or bank (for 3-phase units).
3. Select
3. Select
Overload Alarm Threshold (amps)
,
Near Overload Warning
Threshold (amps)
, or
Low Load Warning Threshold (amps)
.
4. Select
Accept Changes
.
To set the overload outlet restriction, select
Outlet Restriction Configuration
on the
Device manager
menu. For 3-phase units, select a phase or bank to
display and change the
Outlet Phase/Bank Restriction
.
Setting
Description
Overload Alarm
Threshold
Threshold
Set the number of amps that will cause an overload of this phase
or bank.
or bank.
Near Overload
Warning Threshold
Warning Threshold
Set the number of amps at which to generate a warning that the
Rack PDU is nearing overload of a phase or bank.
Rack PDU is nearing overload of a phase or bank.