Lucent Technologies R5SI Manual Do Utilizador

Página de 2643
DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si  
555-230-123  
Issue 1
April 1997
Maintenance Object Repair Procedures 
Page 10-1156
PR-MAINT (Maintenance Processor) 
10
MTP Reset Test (#101)
This test is destructive.
 The test resets the Maintenance/Tape Processor. The 
destructive nature of this test causes the following:
Administration terminal to log off
CDR port to terminate data transmission
Any current tape access to terminate and also to tear down any remote 
access INADS connection
Table 10-345.
TEST #101 MTP Reset Test 
Error 
Code
Test 
Result
Description/ Recommendation
1029 
2014 
2015 
2016 
2017 
2018 
2020 
2022 
2024 
2025 
2051
ABORT
Refer to STBY-SPE Maintenance documentation for a description of these 
error codes.
10102
ABORT
System software resources required for this test are not available.
10104
ABORT
Internal system error
1. Retry the command at 1-minute intervals a maximum of 5 times.
10105
FAIL
The MTP did not respond to being reset.
1. Retry the command at 1-minute intervals a maximum of 5 times.
2. If the test continues to fail, replace the Processor circuit pack.
10106
FAIL
The Maintenance/Tape Processor was reset, but it responded with a NOT 
PASS status, indicating that it did not pass initialization correctly. The MTP 
is not functioning correctly. The system should continue to function, but it 
will not have the ability to save translation to tape, or to read tape if the 
system needs to be rebooted. Environmental monitoring is lost, as is 
communication with the Standby Processor.
1. Retry the command at 1-minute intervals a maximum of 5 times.
2. If test continues to fail, replace the Processor circuit pack.
Continued on next page