Toshiba E6581830 Manual Do Utilizador

Página de 51
 
E658130 
- 12 - 
5. 
Functions 
This option is a communication interface unit that allows the PLC program to operate, monitor   
and set the parameter of the inverter as a remote station of CC-Link. It is able to communicate   
with a maximum speed of 10Mbps not only transmitting bit data but also by word data. 
Moreover, more data transmissions are possible by the use of CC-Link V2.0. 
 
5.1.  Initial setting 
Set the following parameters of the inverter. 
 
Title 
Function Description 
Factory 
setting 
CC-Link 
setting 
cmod 
 
Command mode   
selection 
0: Terminal board 
1: Panel keypad (including remote keypad) 
2: RS485 communication 
3: CANopen communication 
4: Communcation option 
1 4 
fmod
 
Frequency setting 
mode selection 1 
0: Setting dial 1 (save even if power is off) 
1: Terminal board VIA 
2: Terminal board VIB 
3: Setting dial 2 (press in center to save) 
4: RS485 communication 
5: UP/DOWN from external logic input 
6: CANopen communication 
7: Communication option 
8: Terminal board VIC 
9, 10: - 
11: Pulse train input 
12, 13: - 
14: sro
 
0 7 
f856
 
Number of motor   
pole for   
communication 
1: 2 poles 
2: 4 poles 
3: 6 poles 
4: 8 poles 
5: 10 poles 
6: 12 poles 
7: 14 poles 
8: 16 poles 
2 * 
f899
 
Communication 
function reset 
0: - 
1: Reset (after execution: 0) 
0 - 