- 21 - 
5.5.6.  Detail of input and output signals 
1. Output signals (Master -> Inverter) 
The output signals from the master unit are indicated. (Input signals to inverter) 
Device No. 
Signal 
Description 
RYn0 
Forward run command 
OFF: Stop command ON: Forward run command*** 
RYn1 
Reverse run command 
OFF: Stop command ON: Reverse run command*** 
RYn2 
Input terminal function 3(S1) 
The function depends on input terminal selection 3 (c142) *
RYn3 
Input terminal function 4(S2) 
The function depends on input terminal selection 4 (c143) *
RYn4 
Input terminal function 5(S3) 
The function depends on input terminal selection 5 (c144) *
RYn5 
Input terminal function 6(S4) 
The function depends on input terminal selection 6 (c145) *
RYn6 
Input terminal function (PIOFF) 
The function depends on input terminal selection 7 (c146) *
RYn7 
Input terminal function 8(AD1) 
The function depends on input terminal selection 8 (c147) *
RYn8 
Input terminal function 9(ESTP) 
The function depends on input terminal selection 9 (c148) *
RYn9 
Intercept output to inverter   
(Coast stop) 
Stop the output of the inverter when turned on this signal.   
(Stop the output in the secondary circuit) 
RYnA 
Frequency priority CC-Link 
Speed commands are entered from the CC-Link. 
RYnB 
Command priority CC-Link 
Signals from the CC-Link are used to start and stop operation
RYnC 
Monitor command 
When the monitor command (RYnC) is switched on,    each   
monitored values are set to remote registers RWrn, RWrn+1, 
RWrn+4 to RWrn+7 and monitoring flag (RXnC) switches on.
While the monitor command (RYnC) is on, the monitored   
value is always updated. 
RYnD 
Frequency setting command   
(RAM) 
When the frequency setting command (RYnD) is switched 
on, the set frequency RWwn+1 is written to the inverter.   
After the writing completion, frequency setting completion flag 
(RXnD) switches on. 
When the frequency setting command (RYnD) is ON, the set 
frequency is always updated.   
RYnE Reserved** 
Reserved** 
RYnF 
Instruction code execution request
When the instruction code execution request (RYnF) is   
switched on, processes corresponding to the instruction codes 
are set to RWwn+2, RWwn+10, RWwn+12, RWwn+14,   
RWwn+16 and RWwn+18 are executed. 
After completion of instruction code execution, instruction code 
execution completion flag (RXnF) switches on. 
When an instruction code execution error occurs, a value other 
than 0 is set to the reply code (RWrn+2, RWrn+10, RWrn+12, 
RWrn+14, RWrn+16 and RWrn+18) 
The instruction code execution request is effective only when   
this signal changes from OFF to ON. 
Special monitor (72H) is chosen by the instruction code, and 
this signal always updates a monitor value during ON. 
RY(n+1)0 
to Y(n+1)9 
Reserved** Reserved** 
RY(n+1)A  Error reset request 
If the error reset request (RY(n+1)A) is switched on only   
when an inverter fault occurs, the inverter is reset and the  
error status flag (RX(n+1)A) switches off. 
RY(n+1)B 
to RY(n+1)F 
Reserved** Reserved** 
"n" is depend on the station number. 
*    The input terminal function can be changed by the input terminal function selections(
c142
 to c148
). 
 
(But there are functional restrictions. Refer to the following page.) 
** Set OFF (“0”) to reserved bit. 
***When RYn0 and RYn1 are ON simultaneously, the rotation is followed a parameter f105(default = stop).