Toshiba E6581830 Manual Do Utilizador

Página de 51
 
E658130 
- 23 - 
2. Input signal (Inverter -> Master) 
The following shows input signals to the master unit. (The output signals for the inverter.) 
Device No.. 
Signal 
Description 
RXn0 Forward 
running 
OFF: Other than forward running   
(during stop or reverse rotation) 
ON : Forward running   
RXn1 Reverse 
running 
OFF: Other than reverse running 
  (during stop or forward rotation)   
ON : Reverse running 
RXn2 
Output terminal function 1   
(RY-RC) 
The function depends on output terminal function selection 1 
(f130). 
RXn3 
Output terminal function 2 (OUT) 
The function depends on output terminal function selection 2 
(f131). 
RXn4 
Output terminal function 3 (FL) 
The function depends on output terminal function selection 3 
(f132). 
RXn5 Failure 
FL 
OFF : No failure 
ON  : Failure 
RXn6 
PI control OFF 
OFF :
 
PI control permitted   
ON
    : 
PI control prohibited 
RXn7 
Acceleration/ deceleration   
pattern selection (1 or 2) 
OFF: Acceleration/deceleration pattern 1 (AD1) 
ON : Acceleration/deceleration pattern 2 (AD2) 
RXn8 
Emergency stop 
ON : Emergency stop 
RXn9 
Coast stop (ST = OFF) 
OFF : ST = ON   
ON : ST = OFF 
RXnA Alarm 
OFF: No alarm 
ON : Alarm issued 
RXnB Reserved* 
Reserved* 
RXnC Monitoring 
flag 
Switched on when the monitored values are set to RWrn,   
RWrn+1, RWrn+4 to RWrn+7 by the monitor command   
(RYnC) switching on. Switched off when the monitor   
command (RYnC) is switched off. 
RXnD 
Frequency setting completion flag
(RAM) 
Switched on when the set frequency is written to the inverter 
by the frequency setting command (RYnD) switching on. 
Switched off when the frequency setting command (RYnD) 
is switched off. 
RXnE Reserved* 
Reserved* 
RXnF 
Instruction code execution   
completion flag 
Switched on completion of the processing corresponding to 
the instruction code (RWw+2) which is executed when the   
instruction code execution request (RYnF) switches on.   
Switched off when the instruction code execution completion 
flag (RXnF) is switched off. 
RX(n+1)0 
to RX(n+1)9 
Reserved* Reserved* 
RX(n+1)A Error 
status 
flag 
Switched on when occurred an inverter error or option error 
(watchdog error, CPU error, ROM error or RAM error). 
It is not switched on besides that. 
RX(n+1)B Remote 
station 
ready 
Switched on when the inverter goes into the ready status on 
completion of initial setting after power-on or hardware reset. 
(Used as an interlock for read/write from/to the master.)   
Switched off when an inverter error occurs (protective 
function is activated). 
RX(n+1)C 
to RX(n+1)F 
Reserved* Reserved* 
"n" is depend on the station number. 
* The bit described "
 Reserved
 " is unstable. Don't use the “
Reserved