2.When two or more inverters are connected 
 
The following example explains the causes and corrective actions for fault which may be 
judged from the LED status of the CC-Link units (CCL003Z) of the inverters under the 
condition that the SW, M/S and PRM LEDs of the master unit are off (the master unit setting is 
proper) in the system configuration shown below: 
 
 
 
 
PS: 
Power 
supply 
LED Status 
CCL003Z 
Master 
Station 
1 Station 
2 Station 
Cause Corrective 
Action 
L.RUN 
  L.RUN 
  L.RUN 
SD 
  SD 
  SD 
RD 
  RD 
  RD 
L.ERR 
  L.ERR 
  L.ERR 
Normal 
L.RUN 
  L.RUN 
  L.RUN 
SD 
  SD 
  SD 
RD 
  RD 
  RD 
TIME○ 
LINE○ 
or 
TIME● 
LINE○ 
L.ERR 
  L.ERR 
  L.ERR 
Poor contact of the   
CCL003Z with the   
Inverter or the power   
supply is not supplied. 
Plug the CCL003Z   
securely.  
Check the connector. 
L.RUN 
  L.RUN 
  L.RUN 
SD 
  SD 
  SD 
RD 
  RD 
  RD 
L.ERR 
  L.ERR 
  L.ERR 
Since the L.RUN LEDs   
of station 2 and later are   
off, the communication   
cable between the unit 1 
and 2 is open or   
disconnected from the   
terminal block. 
Referring to the LED   
"on" condition, search 
for an open point and 
repair. 
L.RUN 
  L.RUN 
  L.RUN 
SD 
  SD 
  SD 
RD 
  RD 
  RD 
L.ERR 
 L.ERR 
 L.ERR 
The communication   
cable is shorted. 
Among the three wires 
of the communication 
cable, search for   
shorted wire and   
repair. 
L.RUN 
  L.RUN 
  L.RUN 
SD 
  SD 
  SD 
RD 
  RD 
  RD 
TIME● 
LINE● 
or 
TIME○ 
LINE● 
L.ERR 
  L.ERR 
  L.ERR 
The communication   
cable is wired improperly. 
Check the wiring on   
CCL003Z terminal   
block and correct the   
improper wiring point. 
:
On, 
○:
OFF,  ◎:
Flicker, 
*:
 Any of on, flicker or off.
 
 
                      
Master 
          CPU        Unit
 
Station
Inverter
Station
Inverter
Station
Inverter