LST BC06-1 Manual Do Utilizador

Página de 4
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
BC06_DBL_LST_EN_0826.PDF • PAGE 2
A
Building Safety. Building Security.
Clear Concept
The Fire Detection Control Panels BC06-1 and BC06-2 
have been designed for use in small fi re detection sys-
tems and already in the basic version they provide the 
following features:
•   4 conventional detector lines permit the connection 
of automatic detectors and manual call points in con-
ventional technology as well as special detectors with 
contact output. Each detector line can be individually 
parameterised as detector zone for fi re alarms or as 
detector zone for fault messages.
•   If automatic detectors and manual call points are con-
nected together on one detector line, their activati-
ons can be differentiated and evaluated differently by 
the control panel. To this aim, the manual call points 
must be equipped with a special coding module.
•   A  slot  for  connecting  the  Zone  Extension  Board 
ZEB2-1  is  available  to  facilitate  the  extension  to  6 
conventional detector lines.
   The installation of the zone extension board is auto-
matically detected by the control panel and the corre-
sponding parameters are set to initial values.
•   Two individually monitored, separately activated siren 
outputs with an output current of 1A and 0.5A respec-
tively, allow for the connection of acoustic or optical 
signalling devices. When parameterised accordingly, 
the siren outputs can also be operated as evacuation 
circuits.
•   Dry relay outputs indicate the alarm and fault conditi-
ons of the control panel. In addition, 8 open-collector 
outputs with fi xed preset functions as well as two au-
xiliary inputs whose parameters can be freely set are 
available for general control tasks.
•   Logical combinations of detector zones for the acti-
vation of external alarming devices allow for a high 
degree  of  fl exibility.  Thus,  no  additional  expenses 
arise for external relays or logic gates. Thanks to the 
wide range of parameterisation possibilities, individu-
al requirements even under the most diffi cult ambient 
conditions  can  be  combined  into  a  reasonable  fi re 
protection strategy.
•   All events that occur can be output in English via a 
connected printer or PC. Thus, all system conditions 
and user operations that occurred are documented in 
a clearly laid out way.
•   The Fire Detection Control Panel BC06-2 includes a 
4-digit, non-resettable alarm counter which indicates 
the total number of alarms by means of an LC display 
in the operating fi eld.
•   A possible breakdown of the central processing board 
is securely detected and displayed by the system.
•   The processor-monitored power supply ensures per-
manent  supervision  and  charging  of  the  batteries. 
This way, even during a power failure the untroubled 
and uninterrupted operation (for more than 72 hours 
depending on the design of the batteries) is guaran-
teed.
•   Three hierarchised authorization levels for operation 
and parameterisation provide a high degree of secu-
rity against unauthorized access.
•   The control panel is easily operated and the parame-
ters are set via the display and operating fi eld. LEDs 
indicate the current menu and the selected parame-
ter. This facilitates user guidance during commissio-
ning, operation and maintenance.
•   The initial commissioning of the control panel is sig-
nifi cantly facilitated by the practical factory settings. 
This  guarantees  easy  and  time-saving  commissio-
ning.
The extremely fl at wall-mount cabinet allows for an easy 
mounting in virtually any place of the building. Thanks to 
its modern, ageless design, architectural requirements 
and demands of the respective regulations are ideally 
combined. Thanks to the compact design, the standard 
case can accommodate batteries with up to 7Ah also 
in the event of full extension (central processing board, 
optional zone extension board and an auxiliary module) 
of the control panel. Series BC06 thus stands for modu-
larity and easy expansion.
This  product  complies  with  all  relevant  standards  of 
EN 54 and is tested by the VdS. LST‘s high quality level 
is secured by a permanently monitored quality manage-
ment system certifi ed to ISO 9001.