A
Building Safety. Building Security.
Permanent Connection
A variety of peripheral devices can be connected to the 
Fire Detection Control Panel Series BC06:
• Acoustic and optical signalling devices
• Fire controls
• External protocol printer
•  Transmitting devices for alarm transmission
 – and much more.
Evacuation functions
In order to comply with different country-specifi c require-
ments, the control panel can be equipped with an evacu-
ation  function  for  the  manual  activation  of  the  alarming 
devices  also  without  fi re  alarm  (evacuation  alarm).  This 
function is determined by the installer during parameteri-
sation. Two modes of operation are available therefor:
•   With  the  „Evacuate  function“  the  undelayed  activation 
of the desired alarming device occurs by pressing the 
corresponding „Alarming“ button and is indicated by a 
red LED. Pressing the button once again will silence the 
alarming device again, regardless of as to whether the 
evacuation alarm has been triggered by a fi re alarm or 
manually.
•   For the „Evacuation circuit / NEN 2575“, additional ope-
rating buttons for the operation of the evacuation circuit 
are enabled during commissioning. An optional front foil 
is used for the labelling of these buttons. This function 
always acts on both alarming devices. In order to acti-
vate the alarming devices, the „Enable“ button must be 
pressed in addition to the „Activate EV circuit“ button. 
The  alarming  devices  are  silenced  again  by  pressing 
the „Silence EV circuit“ button. The condition of the alar-
ming devices is indicated via LEDs.