Puls UC10.242 DIN-Rail UPS Guia De Especificação

Página de 27
 
 
UC10.241, UC10.242
 
 
UC-Series 
24V,
 
15A,
 
C
APACITOR
-
BASED 
B
UFFER 
M
ODULES
 
 
 
13.  T
ERMINALS AND 
W
IRING
 
 
The terminals are IP20 finger safe constructed and suitable for field and factory wiring. 
 
 
Input and output 
Signals 
Type 
bi-stable quick-connect spring-clamp 
terminals 
pluggable spring-clap terminals 
Solid wire 
0.5-6mm
2
 0.2-1.5mm
2
 
Stranded wire 
0.5-4mm
2
 0.2-1.5mm
2
 
American Wire Gauge 
AWG 20-10 
AWG 24-14 
Max. wire diameter 
2.8mm (including ferrules) 
1.5mm (including ferrules) 
Wire stripping length 
10mm / 0.4inch 
8mm / 0.3inch 
Screwdriver - 
2.5mm 
slotted 
 
Fig. 13-1     Connecting a wire 
Instructions: 
a)  Use appropriate copper cables that are designed for 
minimum operating temperatures of:  
60°C for ambient up to 45°C and  
75°C for ambient up to 60°C minimum 
90°C for ambient up to 70°C minimum. 
b)  Follow national installation codes and installation 
regulations! 
c)  Ensure that all strands of a stranded wire enter the terminal 
connection! 
d)  Unused terminal compartments should be securely 
tightened or closed. 
e)  Ferrules are allowed. 
 
1. Insert the wire
2. Close the lever
14/27
To disconnect wire:
reverse the procedure
 
 
 
Apr. 2014 / Rev. 2.0 DS-UC10.241-EN (REVC) 
All parameters are specified at 24V, 10A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany