Puls UC10.242 DIN-Rail UPS Guia De Especificação

Página de 27
 
 
UC10.241, UC10.242
 
 
UC-Series 
24V,
 
15A,
 
C
APACITOR
-
BASED 
B
UFFER 
M
ODULES
 
 
 
15.  EMC 
The buffer module is suitable for applications in industrial environment as well as in residential, commercial and light 
industry environment without any restrictions. A detailed EMC report is available on request. 
 
EMC Immunity 
According generic standards: EN 61000-6-1 and EN 61000-6-2 
Electrostatic discharge  
EN 61000-4-2 
contact discharge *) 
air discharge *) 
8kV 
15kV 
Criterion A 
Criterion A 
Electromagnetic RF field 
EN 61000-4-3 
80MHz-2.7GHz 
10V/m 
Criterion A 
Fast transients (Burst) EN 
61000-4-4 
input 
lines 
output lines 
signals **) 
2kV 
2kV 
2kV 
Criterion A 
Criterion A 
Criterion A 
Surge voltage on input 
EN 61000-4-5 
+ Æ - 
+ / - Æ chassis ground 
500V 
1kV 
Criterion A 
Criterion A 
Surge voltage on output 
EN 61000-4-5 
+ Æ - 
+ / - Æ chassis ground 
500V 
1kV 
Criterion A 
Criterion A 
Surge voltage on inhibit 
input, ready- and buffering 
contacts and PC-mode 
selector 
EN 61000-4-5 
signals Æ chassis ground 
1kV 
Criterion A 
Conducted disturbance 
EN 61000-4-6 0.15-80MHz 
10V 
Criterion 
*)   Chassis ground connection earthed (grounded) 
**)  Tested with coupling clamp 
Criterions: 
A:    Buffer module shows normal operation behavior within the defined limits.  
 
 
EMC Emission 
According generic standards: EN 61000-6-3 and EN 61000-6-4  
Conducted emission 
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1 
input lines 
limits for DC power ports acc. 
EN 61000-6-3 fulfilled 
 
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1 
output lines 
limits for DC power ports acc. 
EN 61000-6-3 fulfilled 
Radiated emission 
EN 55011, EN 55022 
 
Class B 
This device complies with FCC Part 15 rules. 
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this 
device must accept any interference received, including interference that may cause undesired operation. 
 
 
Switching Frequencies 
The unit has two converters with two different switching frequencies and one switch-
mode current limiter included. 
Switching frequency 1 
100kHz 
Boost Converter (active only in buffer mode) 
Switching frequency 2 
78kHz 
Electronic output current limitation 
Switching frequency 3 
19.5kHz 
Charger 
 
Apr. 2014 / Rev. 2.0 DS-UC10.241-EN (REVC) 
All parameters are specified at 24V, 10A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 