Puls UC10.242 DIN-Rail UPS Guia De Especificação

Página de 27
 
 
UC10.241, UC10.242
 
 
UC-Series 
24V,
 
15A,
 
C
APACITOR
-
BASED 
B
UFFER 
M
ODULES
 
 
 
14.  F
RONT 
S
IDE AND 
U
SER 
E
LEMENTS
 
 
 
Fig. 14-1   Front side (UC10.241) 
 
E Diagnosis 
LED 
(yellow)  
Helps troubleshooting and indicates the following:
- Current Overload: output voltage below 20Vdc 
   due to a too high output current,  
   ready contact is open 
- High Temperature: signal for too high capacitor 
   temperature (>65˚C), charging and buffering is 
   still possible, ready contact is open 
- Buffer Time Expired: 
   buffering stopped due to discharged capacitors 
- Inhibit Active: buffering is blocked by the inhibit 
   signal 
 
Flashing pattern for the yellow diagnosis LED: 
 
1
0
Current
Overload
1
0
High
Temperature
1
0
Buffer time
expired
1
0
Inhibit
active
 
 
F “Warning” 
LED 
(red)  
- Check Input Voltage: 
   Indicates a too low or too high input voltage. 
   The input voltage must be between 23Vdc and  
   30Vdc to turn-on the output and to start 
   charging of the capacitors. 
- PC-Mode Activated 
   Indicates, that the PC-Mode (see also section 9) is
   activated. 
 
Flashing pattern for the red warning LED: 
 
Check input
voltage
1
0
1
0
PC-Mode
activated
 
 
 
 
A
UU
 Input 
Terminals (quick-connect spring-clamp terminal) 
 
UU
B
UU
 Output Terminals (quick-connect spring-clamp terminal)
The minus-pole has the same reference as the minus-pole 
of the input terminals 
 
C
UU
 Signal 
Connector 
(plug connector)  
- Ready: contact is closed when status LED indicates ready 
- Buffering: contact is closed during buffering 
- Inhibit:  a voltage applied on this input signal disables 
                 buffering (e.g. during service) 
- PC-Mode: To activate the PC-mode connect the two pins of  
                    the signal connector together; see also section 9
 
D Status 
LED 
(green)  
- Ready: capacitors are fully charged, no failures detected 
- Charging: capacitors are being charged  
- Buffering: capacitors are being discharged 
 
Flashing pattern for the green status LED: 
G Chassis 
Ground 
 (screw) 
Use a M4 ring-type terminal to connect the 
housing to ground, when required 
1
0
Ready
1
0
Charging
1
0
Buffering
 
 
Apr. 2014 / Rev. 2.0 DS-UC10.241-EN (REVC) 
All parameters are specified at 24V, 10A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
15/27