Puls UC10.242 DIN-Rail UPS Guia De Especificação

Página de 27
 
 
UC10.241, UC10.242
 
 
UC-Series 
24V,
 
15A,
 
C
APACITOR
-
BASED 
B
UFFER 
M
ODULES
 
 
 
16.  E
NVIRONMENT
 
 
Operational temperature 
*)
 
-40°C to +60°C (-40°F to 140°F) 
 
Storage temperature 
-40 to +70°C (-40°F to 158°F) 
for storage and transportation 
Humidity 
**)
 
5 to 95% r.H. 
IEC 60068-2-30 
Vibration sinusoidal 
2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g 
***)
 
2 hours / axis 
IEC 60068-2-6 
Shock 
30g 6ms, 20g 11ms 
***)
 
3 bumps / direction, 18 bumps in total 
IEC 60068-2-27 
Altitude 
0 to 6000m (0 to 20 000ft) 
Approvals apply only up to 2000m 
Over-voltage category 
III 
IEC 62103, EN 50178, altitudes up to 2000m  
 
II 
altitudes from 2000m to 6000m 
Degree of pollution 
IEC 62103, EN 50178, not conductive 
LABS compatibility 
The unit does not release any silicone 
or other LABS-critical substances and 
is suitable for use in paint shops. 
LABS compatibility 
*)   Operational temperature is the same as the ambient or surrounding temperature and is defined as the air temperature 2cm below the 
unit. 
**)   Do not energize while condensation is present 
***) Higher levels allowed when using the wall mounting bracket ZM2.WALL 
 
 
Fig. 16-1   Output current vs. ambient temp. 
 
 
 
0
-40
0
+40
+60°C
2.5
5.0
7.5
10.0
12.5
15A
Ambient Temperature
Allowable Output Current
 
 
 
 
Apr. 2014 / Rev. 2.0 DS-UC10.241-EN (REVC) 
All parameters are specified at 24V, 10A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
17/27