22.  A
PPLICATION 
N
OTES
 
22.1.  E
XTERNAL 
I
NPUT 
P
ROTECTION
 
The buffer module is tested and approved for branch circuits up to 50A. An external protection is only required, if the 
supplying branch has an ampacity greater than this. If an external fuse is necessary or utilized, minimum requirements 
need to be considered to avoid nuisance tripping of the circuit breaker. A minimum value of 20A B- or C-Characteristic 
breaker should be used. 
Check also local codes and local requirements. In some countries local regulations might apply. 
 
 
22.2.  O
UTPUT 
C
IRCUIT 
B
REAKERS
 
The output of the buffer module is equipped with an electronic current limitation. An overload or short-circuit on the 
output is electronically protected and cannot cause any harms, independent of which sizes of power supplies are used 
on the input of the buffer module. 
However, some applications require branch circuit or branch circuit conductor protection. Therefore standard 
miniature circuit breakers (MCB’s or UL 1077 circuit breakers) are commonly used on 24V branches. 
MCB’s are designed to protect wires and circuits. If the ampere value and the characteristics of the MCB are adapted to 
the wire size that is used, the wiring is considered as thermally safe regardless of whether the MCB opens or not. 
To avoid voltage dips and under-voltage situations in adjacent 24V branches which are supplied by the same source, a 
fast (magnetic) tripping of the MCB is desired. A quick shutdown within 10ms is necessary corresponding roughly to 
the ride-through time of PLC's. This requires high peak currents to open the circuit breaker in the required time. 
Furthermore, the impedance of the faulty branch must be sufficiently small in order for the current to actually flow. 
The following table has typical test results showing which B- and C-Characteristic MCBs magnetically trip depending on 
the wire cross section and wire length. 
 
 
Fig. 22-1   Test circuit 
 
Maximal wire length
*)
 for a fast (magnetic) tripping: 
 
0.75mm² 1.0mm²  1.5mm²  2.5mm² 
22/27
C-2A 
20m 25m 39m 58m 
C-3A 
12m 14m 24m 39m 
C-4A 
3m 3m 4m 4m 
MCB
Buffer
Module
Output
 
+
-
Load
+
-
Wire length
S1... Fault simulation switch
 
 
 
 
 
S1
 
*) 
Don’t forget to consider twice the distance to the load (or cable length) when calculating the total wire length (+ and – wire). 
 
 
22.3.  P
ARALLEL 
U
SE TO 
I
NCREASE 
O
UTPUT 
C
URRENT
 
Do not use the buffer modules in parallel to increase the output power.  
Apr. 2014 / Rev. 2.0 DS-UC10.241-EN (REVC) 
All parameters are specified at 24V, 10A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany