22.4.  P
ARALLEL 
U
SE FOR 
R
EDUNDANCY
 
Two buffer modules can be paralleled to build a 1+1 redundant system to gain higher system reliability. 
Recommendations for building redundant power systems: 
a) 
Use separate input fuses for each power supply. 
b) 
Set the power supply into “Parallel use” mode if available. 
c) 
Use a redundancy module to decouple the two power sources. 
d) 
Monitor the individual sources. Therefore, use the alarm contacts of the YRM2.DIODE redundancy module. 
(The YRM2.DIODE is suitable for a 10A redundant system) 
e) 
It is desirable to set the output voltages of all power supplies to the same value (± 100mV) or leave it at the 
factory setting. 
 
 
Fig. 22-2   Wiring example for a fully redundant system,  
redundant power supplies and redundant buffer modules 
 
 
+   +
-  -
Power
Supply
24V Output
+   +
-  -
Power
Supply
24V Output
Load
+
-
Failure
Monitor
YRM2.DIODE
+  
-
OUT
 -
IN 1
+  
-
IN 2 IN 1 IN 2
23/27
Ready
Buffering
Inhibit
UC10
Buffer Module
IN
OUT
+
+
-
-
Inhibit
+  
-
R
ead
y
Buf
fe
ri
ng
 M
ode
UC10
Buffer Module
IN
OUT
+
+
-
-
Inhibit
+  
-
R
ead
y
Buf
fe
ri
ng
 M
ode
 
 
22.5.  P
ARALLEL 
U
SE FOR 
L
ONGER 
B
UFFER 
T
IMES
 
Buffer modules can be paralleled to extend the buffer time. 
 
 
Fig. 22-3   Wiring example for parallel use for longer buffer times 
 
 
+   +
-  -
Power
24V Output
Supply
Load
+
-
Ready
Buffering
Inhibit
UC10
UC10
UC10
Buffer Module
IN
OUT
+
+
-
-
Buffer Module
IN
OUT
+
+
-
-
Buffer Module
IN
OUT
+
+
-
-
Inhibi
t
+  -
Re
a
dy
Buf
fe
ri
ng
Inhibi
t
+  -
Re
a
dy
Buf
fe
ri
ng
Inhibi
t
+  -
Re
a
dy
Buf
fe
ri
ng
C Mode
C Mode
C Mode
 
Apr. 2014 / Rev. 2.0 DS-UC10.241-EN (REVC) 