Puls UC10.242 DIN-Rail UPS Guia De Especificação
UC10.241, UC10.242
UC-Series
24V,
15A,
C
APACITOR
-
BASED
B
UFFER
M
ODULES
22.8. E
XTERNAL
C
ONTROLLED
D
ELAYED
S
HUT
-
DOWN
If the reset is supposed to be controlled by the PC or another external trigger and not the buffer module, the
following wiring option is possible but requires an external relay:
following wiring option is possible but requires an external relay:
Fig. 22-6 Wiring scheme for an external controlled reset after a buffer event
25/27
+ +
- -
Power
Supply
24V Output
UC10
Buffer Module
IN
OUT
+
+
-
-
Inhibit
+
-
R
ead
y
B
u
fferin
g
M
ode
Relay
with NC
contact
with NC
contact
Power Supply Output
Buffer Module Output
5s
70s
PC-Mode
Pin 7 & 8
connected
unit is in "waiting mode" for
a trigger on the inhibit input
a trigger on the inhibit input
Inhibit Input
>250ms
Ready
Contact
Contact
closed
External signal to start
the delayed shut-down
the delayed shut-down
Load
+
-
open
closed
Buffering
Contact
Contact
open
<1s
full
empty
Capacitor
Pin 7 & 8
open
Ready Threshold
250ms
Activation of the “external control mode”:
The PC-Mode pins need to be connected together during a normal mode operation. This connection must be opened
within the first second of a buffer event to set the buffer module into the “external control mode”. In this mode, a
signal on the inhibit input will not immediately execute a shut-down of the buffer module’s output but will be
delayed by 70s. The output of the buffer module will always be switched off for at least 5s.
within the first second of a buffer event to set the buffer module into the “external control mode”. In this mode, a
signal on the inhibit input will not immediately execute a shut-down of the buffer module’s output but will be
delayed by 70s. The output of the buffer module will always be switched off for at least 5s.
Apr. 2014 / Rev. 2.0 DS-UC10.241-EN (REVC)
All parameters are specified at 24V, 10A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
All parameters are specified at 24V, 10A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany