Puls UB10.241 UPS Guia De Especificação

Página de 23
 
 
 
UB10.241 
 
  USeries 
24V, 10A, DC-UPS 
 
 
 
15.  T
ERMINALS AND 
W
IRING
 
 
Power terminals 
Signal terminals 
   
  Type 
Bi-stable, quick-connect spring-
clamp terminals. IP20 Finger-
touch-proof. Suitable for field- 
and factory installation. Shipped 
in open position. 
Plug connector with screw terminal. Finger-touch-proof 
construction with captive screws for 3.5mm slotted 
screwdriver. Suitable for field- and factory installation. 
Shipped in open position. To meet GL requirements, 
unused terminal compartments should be closed. 
14/23 
 Solid 
wire 
0.5-6mm
2
2
0.2-1.5mm
2
2
 Stranded 
wire 
0.5-4mm
0.2-1.5mm
 AWG 
20-10AWG 
22-14AWG 
  Ferrules 
Allowed, but not required  
Allowed, but not required 
Pull-out force 
10AWG:80N, 12AWG:60N, 
14AWG:50N, 16AWG:40N 
according to UL486E 
Not applicable 
 
  Tightening torque 
Not applicable 
0.4Nm, 3.5lb.in 
  Wire stripping length 
10mm / 0.4inch 
6mm / 0.24inch 
 
Fig. 15-1   Spring-clamp terminals, connecting a wire 
 
 
 
1. Insert the wire
2. Close the lever
To disconnect wire:
reverse the procedure
 
 
Instructions: 
a) 
Use appropriate copper cables, that are designed 
for an operating temperature of 60°C  
b) 
Follow national installation codes and regulations! 
c) 
Ensure that all strands of a stranded wire enter the 
terminal connection!  
 
 
d) 
Up to two stranded wires with the same cross 
section are permitted in one connection point 
 
 
16.  R
ELIABILITY
 
 
  Lifetime expectancy 
min. 
137 400h 
At 10A output current, 40°C 
   
min. 
> 15 years 
At 5A output current, 40°C 
   
min. 
> 15 years 
At 10A output current, 25°C 
  MTBF SN 29500, IEC 61709 
886 000h 
At 10A output current, 40°C 
   
1 482 000h 
At 10A output current, 25°C 
  MTBF MIL HDBK 217F 
397 900 
At 10A output current , 40°C, ground benign GB40 
   
545 000 
At 10A output current , 25°C, ground benign GB25 
The  Lifetime expectancy shown in the table indicates the operating hours (service life) and is determined by the 
lifetime expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours. 
Lifetime expectancy is calculated according to the capacitor’s manufacturer specification. The prediction model allows 
a calculation of up to 15 years from date of shipment. 
MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures and indicates 
reliability of a device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily 
represent the life of a product. 
June. 2010 / Rev. 1.3  DS-UB10.241-EN 
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time  
unless otherwise noted. It is assumed that the input power source can deliver a sufficient output current. 
www.pulspower.com   Phone +49 89 9278 0    Germany