Puls YRM2.DIODE Redundancy Module Guia De Especificação

Página de 18
 
 
YRM2.DIODE
 
 
Y-Series 
DC24-48V,
 
20A,
 
D
UAL 
R
EDUNDANCY 
M
ODULE
 
 
 
1. I
NTENDED 
U
SE
 
This device is designed for installation in an enclosure (according to the requirements of the end-standard) and is 
intended for the general use such as in industrial control, office, communication, and instrumentation equipment. 
Do not use this power supply in aircraft, trains and nuclear equipment where malfunction may cause severe personal 
injury or threaten human life. 
 
 
2. I
NSTALLATION 
R
EQUIREMENTS
 
This device may only be installed and put into operation by qualified personnel. 
This device does not contain serviceable parts. 
If damage or malfunction should occur during installation or operation, immediately turn power off and send unit to 
the factory for inspection. 
Mount the unit on a DIN-rail so that the input terminals are located on the top and the output terminals on the 
bottom of the unit. For other mounting orientations see de-rating requirements of chapter 20.9. in this document. 
This device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do 
not cover the ventilation grid (e.g. cable conduits) by more than 30%! 
Keep the following installation clearances:  
40mm on top, 
20mm on the bottom,  
5mm on the left and right sides are recommended when the device is loaded permanently with more than 50% of the 
rated output current. Increase the side clearance to 15mm in case the adjacent device is a heat source (e.g. another 
power supply). 
 
 
WARNING
  Risk of electrical shock, fire, personal injury or death. 
-  Turn power off before working on the device. Protect against inadvertent re-powering. 
-  Make sure that the wiring is correct by following all local and national codes. 
-  Do not open, modify or repair the unit. 
-  Use caution to prevent any foreign objects from entering the housing. 
-  Do not use in wet locations or in areas where moisture or condensation can be expected. 
-  Do not touch during power-on, and immediately after power-off. Hot surfaces may cause burns. 
 
May 2010 / Rev. 1.2 DS-YRM2.DIODE-EN 
All parameters are specified at 24V, 20A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted 
www.pulspower.com   Phone +49 89 9278 0    Germany 
3/18