Number of inputs 
 
Number of outputs 
 
Input voltage 
nom. 
DC 24-48V 
±25% 
The input circuitry must meet the SELV requirements 
stipulated by IEC/EN/UL 60950-1. 
Input voltage range 
18–60Vdc 
 
Voltage drop, input to output 
typ. 
0.78V 
at 2x5A, see Fig. 3-1
 
 
typ. 
0.85V 
at 1x10A, see Fig. 3-2
 
typ. 
0.85V 
at 2x10A, see Fig. 3-1
Input current 
nom. 
2x 0–10A 
continuous 
 
nom. 
1x 0–20A 
continuous, see note 1 
 
nom. 
2x 10–16A 
for up to 5 seconds 
Peak input current 
max. 
150A 
for maximal 10ms per input 
Output current 
nom. 20A 
continuous 
 
nom. 
20–32A 
for up to 5 seconds 
 max. 
25A at 
continuous 
overload 
or short circuit, see note 2 
Reverse current 
max. 
2mA 
per input, -40°C to +60°C 
Reverse voltage 
max. 
200Vdc 
voltage applied to the output, continuously allowed 
Note 1: 
Each input can be loaded up to 20A. At currents above 10A, the other input should not be loaded. It is preferable to parallel the two 
inputs in order to minimize the power loss in such cases. 
Note 2: 
Ensure that the continuous output current does not exceed 25A. Check the short-circuit current of the power sources and if the 
power source can deliver more than 25A together, use an appropriate fuse on the output. 
 
 
Fig. 3-1   Input to output voltage drop when both inputs draw current  
(typical 1+1 redundant case, when the output voltages of the two units are equal or set into “parallel use” mode) 
 
Voltage Drop, typ.
0mV
200mV
400mV
600mV
800mV
1000mV
5A
15A
20A
10A
Output:
2x5A
2x2.5A
Input:
2x10A
2x7.5A
0
0
Input, Output Current
A... 25°C
B... 60°C
A
B
 
 
V
A
QS/QT10
24V,10A
+
-
QS/QT10
24V,10A
+
-
V
A
I
1
I
2
U
1
U
2
I
1
I
2
=
U
2
U
1
=
Voltage Drop
U
1
=
U
OUT
-
Output
A
V
I
OUT
U
OUT
Variable
Load,
0-20A
YR2 / YRM2
Input 1
Input 2
Output
 
 
Fig. 3-2   Input to output voltage drop when only one input draws current 
 
Voltage Drop, typ.
0mV
200mV
400mV
600mV
800mV
1000mV
5A
15A
20A
10A
0
Output Current
A... 25°C
B... 60°C
A
B
 
 
Voltage Drop
U
1
=
U
OUT
-
Not used or
power supply
with lower
voltage
V
A
QS/QT20
24V,20A
+
-
I
1
U
1
Output
A
V
I
OUT
U
OUT
Variable
Load,
0-20A
Input 1
Input 2
Output
YR2 / YRM2
May 2010 / Rev. 1.2 DS-YRM2.DIODE-EN 
All parameters are specified at 24V, 20A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted 
www.pulspower.com   Phone +49 89 9278 0    Germany 