Puls YRM2.DIODE Redundancy Module Guia De Especificação

Página de 18
 
 
YRM2.DIODE
 
 
Y-Series 
DC24-48V,
 
20A,
 
D
UAL 
R
EDUNDANCY 
M
ODULE
 
 
 
4.  P
OWER 
L
OSSES
 
 
 
 
DC 24V 
 
Power losses 
typ. 
8.8W input: 
2x5A 
 typ. 
9.5W 
input: 1x10A 
 typ. 
18.0W 
input: 2x10A 
Standby power losses 
typ. 
1.0W 
at no output current 
 
 
 
Fig. 4-1   Power losses 
 
 
 
Power Losses, typ.
0
0
5
10
20
4
8
12
16
20
24W
25A
15
Output Current
 
 
 
 
 
 
5.  A
LARM 
C
ONTACTS
 
 
Both input voltages are monitored individually. If one input voltage is too low or completely lost, it will be indicated 
by an alarm relay contact.  
Each input has its own monitoring circuitry and relay contact. 
Alarm threshold 
nom. 
21.5V (±0.5V) 
Relay contact opens immediately after 
the input voltage falls below this value. 
Contact ratings 
min. 
60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A 
input: 1x10A 
 max. 
1mA at 5Vdc 
input: 2x10A 
Isolation voltage 
 
May 2010 / Rev. 1.2 DS-YRM2.DIODE-EN 
All parameters are specified at 24V, 20A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted 
www.pulspower.com   Phone +49 89 9278 0    Germany 
5/18