Puls ML15.241 Power Supply Guia De Especificação

Página de 21
 
 
ML15.241
 
 
MiniLine 
 
24V,
 
0.63A,
 
S
INGLE 
P
HASE 
I
NPUT
 
 
 
14.  E
NVIRONMENT
 
 
Operational temperature 
*)
 
-10°C to +70°C (14°F to 158°F) 
Reduce output power according Fig. 14-1
 
Storage temperature 
-40 to +85°C  (-40°F to 185°F) 
For storage and transportation 
Output de-rating 
0.4W/°C 
60-70°C   (140°F to 158°F) 
Humidity 
**)
 
5 to 95% r.H. 
IEC 60068-2-30 
Vibration sinusoidal 
2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g 
2 hours / axis 
IEC 60068-2-6 
Shock 
30g 6ms, 20g 11ms 
3 bumps / direction, 18 bumps in total 
IEC 60068-2-27 
Altitude 
0 to 6000m  (0 to 20 000ft) 
Reduce output power or ambient temperature 
above 2000m sea level. 
Altitude de-rating 
1W/1000m or 5°C/1000m 
above 2000m (6500ft), see Fig. 14-2
Over-voltage category 
III 
IEC 62103, EN 50178, altitudes up to 2000m  
 
II 
Altitudes from 2000m to 6000m 
Degree of pollution 
IEC 62103, EN 50178, not conductive 
*)   Operational temperature is the same as the ambient temperature and is defined as the air temperature 2cm below the unit. 
**)   Do not energize while condensation is present 
 
 
Fig. 14-1   Output current vs. ambient temp. 
 
Fig. 14-2   Output current vs. altitude at 24V 
 
0
12/21
-10
0
20
40
70°C
2.5
5.0
7.5
10.0
12.5
15W
60
Ambient Temperature
Allowable
Output Power
 
0
0
2000
4000
6000m
2.5
5.0
7.5
10.0
12.5
15W
Altitude
A... Tamb < 60°C
B... Tamb < 50°C
C... Tamb < 40°C
A
B
C
Allowable
Output Power
 
 
 
15.  P
ROTECTION 
F
EATURES
 
 
Output protection 
Electronically protected against overload, no-load and short-circuits 
*)
 
Output over-voltage protection typ. 
34Vdc 
max. 37Vdc 
In case of an internal power supply fault, a redundant 
circuit limits the maximum output voltage. In such a 
case, the output shuts down and stays down until the 
input voltage is turned off and on again. 
Output over-current protection electronically 
limited 
 
Degree of protection 
IP 20 
EN/IEC 60529 
Penetration protection 
> 2.5mm in diameter 
e.g. screws, small parts 
Over-temperature protection 
Not included 
 
Input transient protection 
MOV 
Metal Oxide Varistor 
Internal input fuse 
T3.15A H.B.C. 
not user replaceable 
*)   In case of a protection event, audible noise may occur. 
Oct. 2009 / Rev. 1.2  DS-ML15.241-EN 
All parameters are specified at 24V, 0.63A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany